background image

-BL296*B16F*4A20 8/11-

[Input/Output Circuit Configuration and Electrical Properties]

6.8k

24V

1

DN (black)

D P(Red)

Switch, sensor, etc. 
(2-wire type)

IN

4

24V

1

OUT

4

0V

3

24V (Green)

0V (White)

DN (black)

D P(Red)

24V (Green)

0V (White)

DN (black)

D P(Red)

24V (Green)

0V (White)

Load

6.8k

24V

1

24V

OUT

0V

IN

4

0V

3

4-wire (insulated) NPN input
BL296SB-16F-4A-20

4-wire (insulated) ASLINK terminal 

(AnyWire series power supply)

Load by external type 

power supply

[Ex.]
  Use with the common value set at 0V.

BL296XB-16F-4A-20 (Input side)

4-wire (insulated) NPN output
BL296SB-16F-4A-20

BL296XB-16F-4A-20 (Output side)

Inter

nal cir

cuit

Inter

nal cir

cuit

Inter

nal cir

cuit

Contr

ol cir

cuit

In the case of connecting with a load 
(input/output port, etc.) controlled by a 
power supply different from the power 
supply used with AnyWireASLINK, 
make sure to use a 4-wire (insulated) 
terminal.
Otherwise a malfunction may occur.

In the case of an 
inductive load, mount a 
surge killer.

If the power is turned 
on with the circuit 
between OUT and 24V 
shorted, passive 
elements may be 
damaged.

<Circuit conditions>

Rated input voltage 

:  24V DC

Maximum switching current  :  3.5mA

ON current 

:  2.2mA or more

OFF current 

:  1mA or less

ON voltage 

:  (24V-IN) 16V or more

OFF voltage 

:  (24V-IN) 8V or less

Allowable 24V current  :  (24V-0V) up to 1A (per terminal)

<Circuit conditions>

Withstand voltage 

: 30V DC

Maximum ON current : 100mA

CAUTION

DN (black)

D P(Red)

24V (Green)

0V (White)

24V

1

24V

OUT

0V

IN

4

4-wire (insulated) ASLINK terminal 

(AnyWire series power supply)

Load by external type 

power supply

[Ex.]
  Use with the common value set at 0V.

Inter

nal cir

cuit

In the case of connecting with a load 
(input/output port, etc.) controlled by a 
power supply different from the power 
supply used with AnyWireASLINK, 
make sure to use a 4-wire (insulated) 
terminal.
Otherwise a malfunction may occur.

CAUTION

Contr

ol cir

cuit

Содержание BL296 B-16F Series

Страница 1: ...ay occur Use a stable 24V DC power supply Use of an unstable power supply may cause problems with the system Although the AnyWireASLINK has a high noise margin keep the transmission line and I O cable...

Страница 2: ...ocation where the atmosphere is free of corrosive gas flammable gas and sulfur Location where the unit is removed from high voltage or high current cables Location where the unit is removed from cable...

Страница 3: ...VE POWER IN SLAVE General purpose power supply filter Use it if necessary General purpose power supply filter Use it if necessary Insert the ASLINK filter Type ANF 01 regardless of installation method...

Страница 4: ...0V PE 24V 0V 24V 0V PE DP DN 24V 0V DP DN 24V 0V 4 wire terminal 4 wire terminal A B Power supply to the entire system Local power supply branching LINE LOAD LINE LOAD AnyWireASLINK master AnyWireASLI...

Страница 5: ...ddress writer The port cannot be seen from the surface The state in which the installation dedicated DIN rail adapter is mounted and fixed in the same direction as the DIN rail The state in which the...

Страница 6: ...10P 4 3 2 1 A B C Cover Pressure weld using a dedicated tool so that the fittings of the body are in the holes of the cover After pressure welding make sure to check that hooks to are securely engaged...

Страница 7: ...damaged Check if the master unit is powered and if necessary please contact our helpdesk 3 If the LINK of the master unit does not flash check if the master unit is powered Other system errors may als...

Страница 8: ...to use a 4 wire insulated terminal Otherwise a malfunction may occur In the case of an inductive load mount a surge killer If the power is turned on with the circuit between OUT and 24V shorted passiv...

Страница 9: ...rminal Otherwise a malfunction may occur In the case of an inductive load mount a surge killer If the power is turned on with the circuit between OUT and 24V shorted passive elements will be damaged C...

Страница 10: ...00Vp p pulse width 1 s Do not preserve or use under an environment pressurized equal to or higher than the atmospheric pressure at the altitude of 0m Power supply voltage use Transmission method Synch...