-BL296*B16F*4A20 3/11-
■
AnyWire Type: ANF-01 Connection example
■
Filter allowable power current
DP
DN
24V
0V
POWER IN
SLAVE
LG
24V
0V
L
N
FG
~
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
BT0
ANF-01
24V DC stabilized
power supply
General-purpose power
supply filter
(Use it if necessary.)
24V
0V
L
N
FG
~
24V DC stabilized
power supply
4-wire
terminal
4-wire
terminal
2-wire
terminal
If any of the side-by-side lines of DP, DN, 24V and 0V exceeds the total length of 50m
24V
0V
24V
0V
PE
24V DC stabilized
power supply
ANF-01
ANF-01
DP
DN
24V
0V
LG
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
BT0
DP
DN
DP
DN
24V
0V
4-wire
terminal
2-wire
terminal
4-wire
terminal
2-wire
terminal
4-wire
terminal
4-wire
terminal
4-wire
terminal
4-wire
terminal
DP
DN
24V
0V
24V
0V
L
N
FG
24V
0V
24V
0V
PE
24V
0V
24V
0V
PE
DP
DN
24V
0V
DP
DN
24V
0V
A
B
①
Power supply to the entire system
②
Local power supply/branching
AnyWireASLINK master
AnyWireASLINK master
POWER IN
SLAVE
POWER IN
SLAVE
General-purpose power
supply filter
(Use it if necessary.)
~
General-purpose power
supply filter
(Use it if necessary.)
Insert the “ASLINK filter [Type ANF-01]” regardless of installation method and distance when complying with CE Standard.
If any of the side-by-side lines of DP, DN, 24V and 0V exceeds the total length of 50m in a power supply system to be supplied, serially connect
the “ASLINK filter [Type ANF-01]” or “filter of COSEL Co., Ltd. [Type EAC-06-472]” to 24V and 0V in the starting position of the side-by-side lines.
This will improve noise resistance, reduce the impact of crosstalk by transmission signals and stabilize the signals.
In any case of power supply to the entire system from the master driving power supply or power supply from the local power supply, insert a filter.
[Precautions for use with 4-Wire (Insulated) Terminal]
ASLINK filter
ANF-01
MAX 5A/24V DC
Filter of COSEL Co., Ltd. EAC-06-472 MAX 6A/24V DC
Model
Type
Allowable power current
If any of the
side-by-side lines of DP,
DN, 24V and 0V
exceeds the total length
of 50m
If (A+B) of the side-by-side lines of DP,
DN, 24V and 0V exceeds the total length
of 50m