-BL287*B02F*CC20 9/16-
BL287SB-02F –
BL287PB-02F –
BL287SB-02FS –
Brown: 24V
Black: OUT
BL287XB-02F –
Brown: 24V
Black: OUT
BL287XB-02FS –
BL287PB-02FS –
LINK
ALM
Brown: 24V
Blue: 0V
Brown: 24V
Black: OUT
Brown: 24V
Blue: 0V
Brown: 24V
Black: IN
Blue: 0V
Brown: 24V
Black: IN
Blue: 0V
Black: OUT
Blue: 0V
Address setting
Address setting
■
Common procedure for address writer operation
[Various Settings]
Be sure to connect to the AnyWireASLINK master unit to use.
ARW-04 (address writer) of Rev. (Ver.) 1.01 or later version, or ARW-03 of Rev. (Ver.)
2.10 or later version is required for address setting.
For the details of the operating method, refer to the product guide of the address writer.
Connect this unit to the AnyWireASLINK master unit.
Set an address with the address writer with the transmission
signal (DP/DN) and power supply (24V/0V) being connected.
An address number is set as a beginning number from which part of the transmission frame is occupied to the terminal.
Set the address number within the range of bit address “0 to 254.”
(For the input/output mixed type, the same address number should be assigned to both input and output.)
- Set the address number so that the area occupied by the terminal does not exceed the transmission points of the master unit.
- Make sure that the address number setting is not duplicated.
- Also, use the address writer to read an address number that has been written in the terminal.
While power is supplied, make sure that
the above lines are not short-circuited.
Short-circuiting the lines may cause a
fault of the unit.
Black: DN
Red: DP
White: 0V
24V DC
*
*
For the power supply to be
connected, be sure to use
a 24V DC stabilized
power supply.
AnyWireASLINK
master
CAUTION
Transmission
signal
Lot No. 19ECBNB
The factory-set address is “bit address 255” or “bit address 511,” which indicates that an address
has not been set.
The factory-set address varies depending on lot No., as follows:
For S/W version “B” or later version: Bit address 511
For S/W version “A” or 3-digit lot No.: Bit address 255
Input and output operations are disabled with the factory-set address.
S/W version
CAUTION
Example:
Green: 24V