Trouble Shooting
Outdoor
Power
Protected Area
Finish
Outdoor
Power
Protected Area
Attach the armature plate and washers
to the Z bracket assembly.
Connecting Diagram
The product must be powered from , regulated, power-limited, power supply.
If power switch is not wired between DC source v) and magnet, it will take a
longer time to de-energize the magnet simulating residual magnetism.
The minimum permissible wire size to be used shall not be less than 22 AWG.
POWER SUPPLY
12/24VDC INPUT
• Required power: 12VDC/500mA ; 24VDC/270mA
• 12 or 24VDC Auto switchable
• Connect positive (+) lead from a power source to Terminal 1.
• Connect negative (-) lead from a power source to Terminal 2.
Wiring Diagram - Sample wiring and applications
*For example, if there is a fire in the building, fail-safe locks
will unlock due to loss of power, allowing personnel to
escape quickly.
KEYPAD
(Outdoor)
DIGITAL
EXIT BUTTON
(Indoor)
(Outdoor)
Key Switch
Access Control Unit
(Fail-Safe*)
Magnetic Lock
Power to Lock
(Indoor)
Door Status Sensor
Indicates the door is in and open or closed
status. Reed switch rated 0.2A/12VDC
Models:
AXM-800MDS
、
AXM-800MDS-TD
AXM-D800MDS
、
AXM-D800MDS-TD
AXM-1200MDS
、
AXM-1200MDS-TD
AXM-D1200MDS
、
AXM-D1200MDS-TD
Orange
White
Brown
: N.O.
: COM.
: N.C.
Reed Switch Contact
Sensor Icon
Visual Indications LED
UnLocked : GREEN
Locked : RED
No power : NO LED
Timer Adjustment
(1~80 seconds)
Relock time delay (Optional)
Ensures the automatic lock mode works after the
door is closed properly and it can be adjusted
from 1 to 80 seconds.
Models:
AXM-800MTD
、
AXM-800MDS-TD
AXM-D800MTD
、
AXM-D800MDS-TD
AXM-1200MTD
、
AXM-1200MDS-TD
AXM-D1200MTD
、
AXM-D1200MDS-TD
NO
NO
COM
COM
NC
NC
1
2
NO
NO
NO
NO
Bond Sensor
Output
Bond Sensor Output
Indicates the Bond and functioning status.
N.C. contact output: Open / Not bonding status.
N.O. contact output: Locked / Bonded status.
Models:
AXM-800M
、
AXM-D800M
AXM-1200M
、
AXM-D1200M
NC
NC
COM
COM
NO
NO
PB
PB
PB
PB
POWER
SUPPLY
KEYPAD
(Outdoor)
DIGITAL
EXIT BUTTON
(Indoor)
Close the door and connect the
power.
After the magnet attracts the armature
plate, adjust the Z bracket to fit the door.
Fasten the Z bracket to the door.
Problem
Door does
not lock
Low holding
force
Possible Cause
Solution
No power
Poor contact between electromagnet
and armature plate
Low voltage or incorrect voltage
setting
Make sure the wires are connected properly
Check that the power supply is connected and working properly
Make sure the lock switch is wired correctly
Check if the armature plate is deformed?
Make sure if the rubber washer was used between magnetic lock and armature plate.
Make sure the contact surfaces of the electromagnet and armature plate are clean
and free from dust and foreign material.
Ensure the electromagnetic lock is set for the correct voltage.
Check for proper voltage at the electromagnet lock input. If low determine if the
correct wire gauge is being used to prevent excessive voltage drop.
(Indoor)
All the field wiring shall be on the secured side (or indoor).