SERVICE MENU:
WIZARD
WELCOME
SETUP WIZARD
Press MENU key to advance through the wizard
ROOM MODE
Set room mode (Negative/Positive)
LOW PRESSURE
ALARM POINT
+/-
0.0001
to +/-
0.1000
in.w.c.
or No Alarm. Default:
+/-
0.0010
in.w.c.
HIGH PRESSURE
ALARM POINT
+/-
0.0001
to +/-
0.1000
in.w.c.
or No Alarm. Default:
+/-
0.0500
in.w.c
.
ALARM DELAY
Set alarm delay time (5-3600 sec). Default 30 seconds
RPI MUTE TIME
(1-1440 minutes). Default: 15 minutes
SETUP WIZARD
COMPLETE
PM has been setup and will now re-boot to apply all settings,
SEE MANUAL
FOR ADV SETUP
See this manual for advanced setup options
PRESS MENU
TO EXIT
NOTE:
The Wizard will force you to go through all settings in order. You can re-run the wizard at any time by
Loading Defaults
in the Diagnostics Menu
. Once you have gone through the Wizard fully, the PM will reset.
AntecControls.com | PM - Manual
8
ROOM PRESSURE MONITOR
DISPLAY NAVIGATION
Wizard Menu
The first time the PM is powered on, the RPI will step through the setup wizard. This allows a quick setup of the
parameters needed. To enter the Setup Wizard, use the passcode DOWN - EMERGENCY - EMERGENCY - MUTE.