ROOM PRESSURE MONITOR

PM Series

MANUAL 

V10

2

 

FIRMWARE

 V3.

84

Содержание PM Series

Страница 1: ...ROOM PRESSURE MONITOR PM Series MANUAL V102 FIRMWARE V3 84 ...

Страница 2: ...ault Sequence of Operations 5 Display Navigation RPI Initial Startup 6 Occupancy Modes Service Menu 6 Monitor 6 Service Menu 7 Wizard Menu 8 Pressure Menu 9 Occupancy Menu 9 Timing Menu 10 Input 10 RPI Setup 11 ROOM PRESSURE MONITOR CAUTION Short circuit or incorrect wiring may permanently damage the controls or other equipment Ensure proper wiring practices The PM is a 24 VAC monitor Do not apply...

Страница 3: ...nterface with true character display LED side bars offer 180 degree viewing of current room status Green Safe Red Danger exceeding low or high alarm set points Blue Unoccupied Password protected menu Easy to use MENU system for fast and simple setup of system Setup Wizard walk through setup of PM when first powered up Room Pressure Sensor RPS Features High accuracy room pressure sensor Range 0 1 i...

Страница 4: ...120 24 VAC 40 VA Transformer QTY 1 019604 003 OPTIONAL 7 Instruction Manual QTY 1 Please ensure you have all compo nents before proceeding Inspect components for shipping damage Do not install any components that appear damaged contact your local Antec Controls Representative for replacements For further information please visit AntecControls com INCLUDED ITEMS 1 RPI STANDARD 2 ROOM PRESSURE SENSO...

Страница 5: ...talled within 12 inches of the Main sensor Note The Main Sensor has a black cable connector and brass airflow nipple while the Reference Sensor only has a brass airflow nipple RPS Main Sensor Assembly Mounted in corridor hallway Gently plug green c25 cable to black quick connection on back Route the RJ 12 telephone type connection back to PM Plug into black RJ12 jack Also firmly attach air tubing ...

Страница 6: ...onnect main power to transformer Confirm voltage input matches transformer label either 120 VAC or 277 VAC 3 Wire 24 VAC hot and common to PM Note the hot and common polarity 3 ROOM PRESSURE MONITOR INSTALLATION AND MOUNTING INSTRUCTIONS TYPICAL WIRING AntecControls com PM Manual CAUTION Image is shown for optional 24 VAC transformer If power is not provided by Antec Controls ensure proper 24 VAC ...

Страница 7: ...he local alarm will turn on Mode Status LCD Display LED Bars Alarm Negative Positive Pressure Monitoring Room Occupied SAFE Pressure reading within LOW HIGH set points Primary Room 0 0123 in w c GREEN OFF Negative Positive Pressure Monitoring Room Occupied ALARM Pressure reading within LOW HIGH set points ALARM 0 0001 in w c RED ON Neutral Room Unoccupied UNOCCUPIED Pressure measured but no alarms...

Страница 8: ...ave and exit Up Down Button Used for menu selection and adjustment press both up and down at same time to display RPI Startup screens Menu Enter Used to Enter service menu s The menu s are password protected Mute Used to temporarily mute the local alarm for a certain number of minutes Emergency Used to trigger emergency mode Local Alarm will sound and BACnet point will change to Alarm alerting the...

Страница 9: ... either negative or positive SERVICE MENU OCCUPANCY Allows user to force occupied unoccupied modes SERVICE MENU TIMING Allows configuration of alarm delays SERVICE MENU INPUT Allows configuration of the room pressure sensor RPI SETUP Allows configuration of the display settings for the RPI SERVICE MENU DIAGNOSTIC Contains diagnostic information or allows the monitor to be reset to factory defaults...

Страница 10: ...been setup and will now re boot to apply all settings SEE MANUAL FOR ADV SETUP See this manual for advanced setup options PRESS MENU TO EXIT NOTE The Wizard will force you to go through all settings in order You can re run the wizard at any time by Loading Defaults in the Diagnostics Menu Once you have gone through the Wizard fully the PM will reset AntecControls com PM Manual 8 ROOM PRESSURE MONI...

Страница 11: ...onitor will enter alarm RED mode if current pressure reading is out of range Default 0 0010 in w c HIGH PRESSURE ALARM 0 015 in w c Monitor will enter alarm RED mode if current pressure reading is out of range Default 0 500 in w c PRESS MENU TO EXIT PRESSURE PRIMARY ROOM SERVICE MENU PRESSURE ROOM MODE ISOLATION Room Mode default will display Setback Isolation This mode can also be displayed as Oc...

Страница 12: ...if a Keyswitch nurse station is con nected SENSOR SCALE FACTOR This allows the primary sensor reading to be ajusted to match a manual reading taking during setup balancing It provides a linear scaling of the sensor reading and is the preferred method of adjustment range 0 500 to 2 000 Default 1 000 SENSOR OFFSET This allows for the pressure reading to be offset by a fixed amount This can be used i...

Страница 13: ...aution conditions Options Off Yellow Blink Yellow Blink Green Default Yellow LIGHT BAR UNOCC SKY BLUE Light Bar in Unoccupied Mode This sets the colour of the light bar while in unoccupied mode Options Off Sky Blue White Default Sky Blue ALARM TYPE WAIL This sets the sound of the alarm Choose from wail 2khz tone red alert no tone Default wail OCCUPANCY NAME OCCUPANCY Selects the text displayed for...

Страница 14: ...current specifications or more detailed information Not all products may be available in all geographic areas All goods described in this document are warranted as described in the Limited Warranty The complete product catalog can be viewed online at AntecControls com Antec Controls by Price is a registered trademark of Price Industries Limited 2020 Printed in Canada v102 ...