Pitched roof mount installation manual – Version 2016 1.0 to AS/NZS1170.2.2011 Amdt 3
–
2012 8
Figure: Panel must be installed flat to the roof
DETERMINE THE HEIGHT OF THE INSTALLATION SITE
This document provides sufficient information for Antaisolar system installation height less than 20 meters.
If your installation site is more than 20 meters in height, please contact Antaisolar to obtain engineering data
to support your installation.
VERIFY ACCEPTABLE RAIL END OVERHANG
Rail end overhang must equal 50 percent or less of foot spacing. Thus, if foot spacing is 1200mm, the
Rail end over hang can be up to 600mm. In this case, two feet can support a rail of as much as 2400mm
(1200mm between the feet and 600mm of overhang at each end).
DETERMINE ROOF SLOPE
Antaisolar mounting system can be used for roof slope up to 60 degrees. This document provides sufficient
information for below 30 degrees, please contact Antaisolar for between 30 and 60 degrees.
DETERMINE THE MAXIMUM RAIL SUPPORT SPACING
Please use the table in certification of compliance to determine the Antaisolar Rail IV support spacing for
installations. Certification of compliance please request from dealer or contact Antaisolar. Below only for
reference.