Antaira Technologies
– Industrial Modbus Gateway
STM-60XC(-T) Series Hardware Manual V1.1
11
Amber, blinking
System is ready (1cycle/sec.)
Off
System is not working
Table 2.1
– LED Indicators for STM-60XC Series
2.6 Power Connection
Warning! Power down and disconnect the power cord before servicing or wiring the serial
device server.
Caution! Do not disconnect modules or cabling unless the power is first switched off.
The device only supports the voltage outlined in the type plate. Do not use any other power
components except those specifically designated for the serial device server.
Caution! Disconnect the power cord before installation or cable wiring.
The STM-60XC series supports dual 12 to 48 VDC power inputs and power-fail relay output.
The following figure,
Figure 2.8
, illustrates a P-Fail alarm application example. The P-Fail alarm
contacts are visible on the front view of the terminal block.
Figure 2.8
Power Wiring for STM-60XC Series
You can connect an alarm indicator, buzzer, or other signaling equipment through the relay output.
The relay opens if power input 1 or 2 fails. In a wiring example where an LED is connected to the
relay output, the LED would be off in an open state
Load
External
Power