Antaira Industrial Ethernet Switches
LNX-0601G-SFP Series User Manual V1.2
11
2.8 Wiring the Fault Alarm Contact
The fault alarm contact is in the middle of the terminal block connector as the picture shows below
in Figure 2.16. By inserting the wires, it will detect the fault status including power failure or port
link failure (managed industrial switch only) and form
a normally open circuit. An application
example for the fault alarm contact is shown below in Figure 2.16.
Note
The wire gauge for the terminal block should range between 12 ~ 24 AWG.
If only using one power source, jump from Pin 1 to Pin 5 and Pin 2 to Pin
6 to eliminate the power fault alarm.
2.9 DIP Switch Settings
The following describes the DIP switch settings (Figure 2.17).
DIP 1:
ON: Disable Energy Efficient Ethernet (EEE)
Off: Enable Energy Efficient Ethernet (EEE)
DIP 2:
ON: Configured to 100-BASE-FX
Off: Configured to 1000-BASE-FX
Note
The device is required to recycle the power, if any current setting has been
changed.
Figure 2.16
Wiring the Fault Alarm Contact
Figure 2.17
DIP Switch