Step 3. Edit An Input Statement’s Properties,
Continued
10-16
Opcode
Qualifier
Application
ION Smoke
Level
Smoke level
0.5
Input statement is TRUE when the smoke level for the referenced ion smoke
detector exceeds 0.5 %.
Smoke level
0.9
Input statement is TRUE when the smoke level for the referenced ion smoke
detector exceeds 0.9 %.
Smoke level
1.3
Input statement is TRUE when the smoke level for the referenced ion smoke
detector exceeds 1.3 %.
Smoke level
1.7
Input statement is TRUE when the smoke level for the referenced ion smoke
detector exceeds 1.7 %.
XPHOTO
Smoke
Level
Smoke level
0.2
Input statement is TRUE when the smoke level for the referenced extra-
sensitive photo smoke detector exceeds 0.2 %.
Smoke level
0.5
Input statement is TRUE when the smoke level for the referenced extra-
sensitive photo smoke detector exceeds 0.5 %.
Smoke level
1.0
Input statement is TRUE when the smoke level for the referenced extra-
sensitive photo smoke detector exceeds 1.0 %.
Smoke level
1.5
Input statement is TRUE when the smoke level for the referenced extra-
sensitive photo smoke detector exceeds 1.5 %.
Smoke level
2.0
Input statement is TRUE when the smoke level for the referenced extra-
sensitive photo smoke detector exceeds 2.0 %.
Smoke level
2.5
Input statement is TRUE when the smoke level for the referenced extra-
sensitive photo smoke detector exceeds 2.5 %.
Smoke level
3.7
Input statement is TRUE when the smoke level for the referenced extra-
sensitive photo smoke detector exceeds 3.7 %.
Table 10-1. Input Opcodes and Qualifiers,
continued