Appendix C: Remote Terminal Access
Operating Modes
68
IQ-636X Operations Manual P/N 52181:A 04/28/2005
Local Terminal Mode (LocT)
Functions, passwords, and special requirements of Local Terminal Mode (LocT) are:
Functions available with the Local Terminal Mode:
Table 19 Local Terminal Mode Functions
Functions:
Read Status, Alter Status, and Control Functions (Table 19).
Passwords:
User-defined password for Alter Status functions.
Requirements:
The terminal must be mounted in a UL 864 listed enclosure or positioned to
provide equivalent protection against unauthorized use.
Function
Lets you...
Read Status
• Display the status of an individual point (Detector, Module, Panel
Circuit, or Zone).
• Display a list of all the points in Alarm or trouble.
• Display a list of all programmed points in the system.
• Step through the History buffer event by event.
• Display the entire History buffer.
Alter Status
• Disable/Enable an individual point.
• Change the sensitivity of a detector.
• Clear the verification counter of all detectors.
• Clear the entire History buffer.
• Set the AWACS alert and action levels.
Control Functions
• Acknowledge.
• Signal Silence.
• System Reset.
• Drill.
Содержание AUTOPULSE IQ-636X
Страница 1: ...A P N 52181 A ECN 05 034 Document 52181 04 28 2005 Rev ...
Страница 8: ...8 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 12: ...12 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 14: ...14 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 20: ...20 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 40: ...40 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 66: ...66 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 84: ......