How to Enter Program Change
Programming
IQ-301 PN 50036:F 10/29/2001
77
The Autoprogram Summary screen appears. You can verify removal of the detector
from the program by noting the new count of detectors as shown in Figure 60.
Figure 62 Sample Autoprogram Summary Screen
5. Press the
ENTER
key, then press the
BACKSPACE
key to save the program in memory
and return to the Program Change screen (Figure 53 on page 71).
How to Change Autoprogram System Defaults
The Autoprogram option automatically selects default system functions during initial
programming of the control panel. You can change the default system functions. If you
change any system default, then autoprogram the control panel, any new system values
that you enter, do not change. For example, if you change a Program Change password,
install new devices, and run the Autoprogram option, the new Program Change
password remains unchanged. Table 18 contains default system functions and value.
Table 18 Default Parameters for System Functions
DETECTORS :10
MODULES :02
PANEL CKTS :04
Note that the number
of detectors
decreases (from 11 to
10) to show the
removal of the
detector.
System Function
Default Value
For more information, refer to
Zone 00
Custom label =
GENERAL
ALARM
ZONE
“How to Edit or Delete a Point (2=point)” on
page 78
Zones 01 through 89
Custom label is blank
“How to Change a Zone Label (5=zones)” on
page 86
Zone 90
Label =
PRESIGNAL
/
PAS
DELAY
,
DELAY
=180,
PAS
=
N
“Programming a Presignal Zone (Z90)” on
page 87
Zones 91-94
Label =
RELEASE
ZONE
91
DELAY
=00,
ABORT
-
ULI
CROSS
=
N
SOAK
=00
“Releasing Control Zones (Zones 91-94)” on
page 88
Zones 95 and 96
Label =
TIME
CONTROL
ZONE
96,
ON
=00:00,
OFF
=00:00,
DAYS
=
SMTWTFSH
“Time Control Change (Zones 95, 96)” on
page 88
Zone 97
Label =
HOLIDAY
ZONE
97
, all days are
00/00
“Holiday Change (Zone 97)” on page 88
Zone 98
Label = all blanks,
CODE TYPE
=
MARCH
TIME
“Code Type (Zone 98)” on page 89
Zone 99
Label =
PRE
-
ALARM
ZONE
99,
ALERT
=70%
OF
ALARM
,
ACTION
=00%
OF
ALARM
“Pre-Alarm (Zone 99)” on page 89
System Parameters
SIL
INH
=000,
AUTO
=000,
VERIFY
=00,
USA
TIME
,
ANNUN
=
NON
SUPV
,
LocT
BLINK
=
Y
,
ST
=4,
AVPS
=
N
“How to Edit System Functions (7=sys)” on
page 89
Programming Passwords
Program Change 00000
Status Change 11111
“Programming Passwords” on page 66
“How to Change a Programming Password
(3=passwd)” on page 85
All Systems Normal Custom
Message
Custom message label = 40 blanks