How to Enter Program Change
Programming
IQ-301 PN 50036:F 10/29/2001
87
3.4.8 How to Edit a Special Zone (6=
SPL
ZONES
)
Purpose of Special Zones (90-99)
Special zones include ten special software zones that you can program to do the
following:.
Table 26 Special Software Zones 90-99
How to Select Special Zones
The Special Zone Change option you change the program for special Zones 90 through
99. From the Program Change screen (Figure 53 on page 71), select
6=SPL ZONES
to
display the Special Zone Change screen. Figure 74 shows the Special Zone Change
screen:
Figure 74 Special Zone Change Screen
From the Special Zone Change screen, you can select one of the options listed in Table
26. To select an option from the Special Zone Change screen, key in the number of the
option. For example, to select the coding software zone, key in “98”; to select the
releasing software zone 92, key in “92”. The following subsections show each screen
that can be selected from the Special Zone Change screen (Figure 74).
Programming a Presignal Zone (Z90)
"
What is a Presignal Zone?
You can use Presignal zone 90 when you want to
delay control points for human verification. If zone 90 is included in a control or relay
module or Notification Appliance Circuit CBE list, it inhibits all other CBE. Detectors
and monitor modules must call out Zone 90 in their program to be included in the
pre-signal/PAS operation.
When any alarm occurs and no PAS inhibit type monitor module is activated, Zone 90
activates. If a second alarm activates, or the Drill switch is pressed, Zone 90 goes false.
If PAS is selected, and the Acknowledge switch is not pressed within 15 seconds, Zone
90 goes false. At the first alarm, a programmable 0–180 second timer starts. If an
Alarm Silence occurs, the timer stops. If the delay timer expires, manual activation will
activate outputs mapped to zone F0. The System Alarm relay, the 4XTM Polarity
Reversal Alarm Output, and the 4XTM Municipal Box Output delay if PAS is selected,
but do not delay for Presignal operations.
Special Zone
Description
90
A software zone used to select Presignal options.
91-94
Four software zones used to control releasing applications.
95, 96
Two software zones used to assign time control functions.
97
A software zone used to select holiday time controls.
98
A software zone used to select the type of coding for Panel Circuits.
99
A zone used to select the Pre-Alarm function.
Program Change
Password
SPECIAL@ZONE@PROGRAM
90=PRESIG@91-94=REL
95-96=TIME@97=HOL
98=CODING@99=PREALM