22
25
Record Fault code
Record enable (default)
Record disable
26
Bulk charging voltage
(C.V voltage)
3.2KVA default setting: 28.2V
5KVA default setting: 56.4V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 25.0V to 31.5V for 3.2KVA model and
48.0V to 61.0V for 5KVA model. Increment of each click is 0.1V.
27
Floating charging voltage
3.2KVA default setting: 27.0V
5KVA default setting: 54.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 25.0V to 31.5V for 3.2KVA model and
48.0V to 61.0V for 5KVA model. Increment of each click is 0.1V.
29
Low DC cut-off voltage
3.2KVA default setting: 21.0V
5KVA default setting: 42.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 21.0V to 24.0V for 3.2KVA model and
42.0V to 48.0V for 5KVA model. Increment of each click is 0.1V.
Low DC cut-off voltage will be fixed to setting value no matter
what percentage of load is connected.
30
Battery equalization
Battery equalization
Battery equalization disable (default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.