User operation      

 

         

                                19 

 

 

                                  MAXXfl o EVO Lite 

3.8.1 Error codes (continued)

 

Error 

Code

Error Code 

Description

Diag. 

Code

   Notes

217

Sensor error

765

766

Short circuit of Ionisation circuit. Check operation of ionisation probe using pa-

rameter 8329 (menu -  Diagnostics heat generation). Ionisation probe may need 

replacing. Check electrical supply to the heater and burner - pay special attention 

to the earth circuit and supply.

317

Grid frequency 

outside permitted 

range

275

461

The frequency (Hz) of the electrical supply is outside permitted tolerance. Check 

electrical supply to heater.

324

Input BX, same 

sensors

110

BX sensor duplicated - Two sensor inputs have been defi ned twice with the same 

sensor type (e.g. B3). Review last parameters programmed to remove duplica-

tion.

325

Input BX/exten-

sion mod, same 

sensors

Any

BX expansion module 1 sensor duplicated - Two sensor inputs have been de-

fi ned twice with the same sensor type (e.g. B3). Review last parameters pro-

grammed for the expansion module to remove duplication.

327

Extension mod, 

same function

Any

AGU2.5 expansion module function duplicated - check parameter setup (in “Con-

fi guration” menu)

335 / 

336

Sensor input 

BX21 / BX22 

without function

211 / 

212

A sensor has been detected connected to BX21 of the AGU2.5 expansion mod-

ule 1, but not defi ned. Defi ne the sensor using the parameters or remove the 

sensor if not required.

All 

other

As above except the undefi ned sensor is connected to an AGU2.5 expansion 

module 1. The AGU2.5 expansion module should be defi ned as module 1 - 

Check the dip switches on the front of the device is set correctly 

384

Extraneous light

252

393

Ionisation current detected before whilst in standby mode. Check ionisation 

current (“Diagnostics producer” parameter 8329). If there is a current present is 

greater than 0.61 whilst the burner is in standby, turn off  gas supply to check gas 

valve is closing completely. If current is still present, remove ionisation probe and 

use a screwdriver to clear the opening through the burner door before replacing 

the probe and testing again.

Persistent errors may indicate that the burner is only operational for very short 

periods. Try increasing the switching di

 erential by at least 1

O

C (parameter 5024) 

to increase burner run time. 

Other

Ionisation current detected during ignition phase before the gas valve is opened.

385

Mains under volt-

age

554

555

Mains voltage below 185v - check electrical supply to the appliance.

386

Fan speed toler-

ance

388

Fan outside allowed speed tolerance during standby phase

531

389

Fan outside allowed speed tolerance during pre-purge phase

374

383

384

Fan outside allowed speed tolerance during ignition phase. 

375

386

Fan outside allowed speed tolerance during min modulation phase. 

385

Fan outside allowed speed tolerance during max modulation phase. 

532

534

382

390

Fan outside allowed speed tolerance during post-purge phase

Other

Check connections and wiring loom of the fan. Replace fan if no fault found. If 

necessary use parameter 9650 Chimney drying mode to test the function of the 

fan without having to operate the burner.

432

Function earth 

not connected

Any

No Ignition earth, X1 / X17 not connected or earth fault. Check internal and exter-

nal earth wiring to the heater

433

Heat exchange 

temperature

Any

Heat exchanger temperature is too high. Investigate all sources of overheating. 

When the issue has been resolved examine the heat exchanger for damage 

before putting back into operation.

NA

DHW Operating 

mode locked 

Any

Check to see if the remote enable link wire is fi tted or external controls wired to 

these terminals are closing this circuit. To activate DHW operation this circuit 

must be closed.

Содержание MAXXflo EVO Lite

Страница 1: ...uctions before commencing installation and leave this manual with the customer for future reference M10226 MAXX o EVO Lite High e ciency condensing stainless steel storage water heater SC15 201 SC25 2...

Страница 2: ...time and date 3 3 Setting DHW operating mode 3 4 Setting DHW temperature 3 5 Setting DHW heating time program 3 6 Temporary DHW operation function 3 7 Information pages 3 8 Error messages 3 8 1 Error...

Страница 3: ...h reduced physical sensory or mental capabilities lack of experience or knowledge Only users given supervision or instruction concerning the safe operation of this heater and understand the hazards in...

Страница 4: ...lve months should be allowed between service inspections The condensate outlet shall not be modi ed or blocked It is recom mended that as part of the regular maintenance the condensate systems is exam...

Страница 5: ...and service engineers 1 2 4 Frost protection This heater is tted with an automatic Frost Protection system Pro vided there is electrical power gas is connected and the heater is not in a lockout condi...

Страница 6: ...een then pushing to select the item When selected the item will be displayed as inverse and can then be changed by rotating and the change is con rmed by pushing enter If the item was selected by mist...

Страница 7: ...perating object is selected and is displayed inverted The lower level is displayed if the operating object consists of multiple levels e g Time program Turn control knob Set value Press control knob C...

Страница 8: ...est heater and system Adjust repair pages Adapt parameters in Complete parameter list Symbol Alarm indicates a system error Symbol Maintenance Special operations indicates the presence of a maintenanc...

Страница 9: ...me 1 Rotate until the settings page symbol is highlighted then press enter Regional settings 1 3 should already be prese lected 2 Rotate to select the time eld then press enter 3 Rotate and enter a ne...

Страница 10: ...t and change the mode to On Using to highlight the Nominal set point press enter and enter a new value and then enter within 3 seconds to con rm 1 1 Domestic Hot Water Operating mode On Temporary Nomi...

Страница 11: ...light the time program eld then press enter to open the time clock setting page Select the day eld to change the times of that day Press to enter screen to set times for that day Domestic Hot Water Op...

Страница 12: ...per day can be set To delete a time band use to move the start and end times of the band to be the same then press enter The time settings of any day can be copied and applied to other days in the wee...

Страница 13: ...enter to highlight the eld Change the Temporary eld from to Recharging and press enter to activate Temporary operation mode Heater operation is now active and will recharge the DHW tank water to the n...

Страница 14: ...mple the screen is showing the status of DHW and the tank temperature To view additional info pages rotate In this example the screen is showing the status of DHW and the temperature of the heated wat...

Страница 15: ...example the heater has gone into a lockout mode because the gas supply has been interrupted The resolution would be to re establish the gas supply to the heater and then reset the error to restart he...

Страница 16: ...on another Siemens controlled appliance Check ad dresses of all Siemens controlled appliances via parameter 6600 83 BSB short circuit 595 No BSB communication or wires shorted Check operation of GUI...

Страница 17: ...return sensors are operating correctly 419 430 813 814 Flow temperature limit exceeded Check for overheating issues and ow sen sor B2 performance 809 810 422 423 Flow temperature not plausible Reading...

Страница 18: ...ace control PCB if no fault found 332 Error when closing gas valve relay Check gas valve and connections from con trols Replace control PCB if no fault found 333 Error when opening gas valve relay Che...

Страница 19: ...there is a current present is greater than 0 61 whilst the burner is in standby turn o gas supply to check gas valve is closing completely If current is still present remove ionisation probe and use...

Страница 20: ...may in future stop if the maintenance message is ignored and an error develops as a result In this example 105 Maintenance message is used to notify the user the heater has been in operation for more...

Страница 21: ...ht regional settings and press enter to select Rotate to select one of the 3 setting pages Default dates mark the start and end of summertime clock adjustment This can be changed if actual dates of ad...

Страница 22: ...eer in additions to the options screens available at end user level Using the Graphical User Interface rotate to select Setup page on the navigation bar and press enter to select In the work area rota...

Страница 23: ...func tion by pressing enter Rotate to eld 7700 Relay test and press enter Rotate to select output to test Press the enter to activate the desired output relay see example above Once the testing has be...

Страница 24: ...r e g the optional web server only one of the connected items can be the clock master If the optional web server is connected to this heater then parameter line 6640 must be changed to Slave without l...

Страница 25: ...he heater as an Engineer to reset these counters see installation and maintenance manual sec tion 9 2 1 1 Input output test Communication Source Consumer Versions Boiler 1 3 8005 State boiler O 8009 S...

Страница 26: ...1 1 Input output test Communication Source Consumer Versions Domestic hot water 2 4 8830 DHW Temp 1 58 6O C 8831 DHW temp setpoint 60 0O C Back Useful parameters viewable PARAMETER DESCRIPTION NOTES 8...

Страница 27: ...screen Highlight Versions by rotating and select the function by pressing enter Details are shown for the software and text versions being used by the GUI this may be useful to establish the level of...

Страница 28: ...Built to perform BAXI HEATING COMMERCIAL BRANDS ALL TOGETHER BETTER 5HJLVWHUHG RI FH DGGUHVV D L HDWLQJ 8 URRNV RXVH RYHQWU 5RDG DUZLFN 9 June 2019 Sales 0345 070 1055 Technical 0345 070 1057 Web andr...

Отзывы: