ANDERSON-NEGELE MPI-200 Скачать руководство пользователя страница 2

C O N T R O L S

2

Supply voltage/power supply

The equipment is delivered with the programming adapter set to a power supply 

from the PC. However, it is also possible to wire the programming adapter into 

the system and program the sensor afterward. To do this, the parameter for the 

power supply must be changed to “External supply”. Proceed as follows:

1.  Select the “Power supply MPI-200” parameter

2.  Press the button 

 and change the power supply parameter from 

“PC M12 not connected” 

to

“External, M12 connected”

 using the arrow button

3.  Press the button  

 to save the change. The mask is refreshed 

MPI-200 power supply

1.

2.

Advice

If the sensor is supplied from the control center/PLC, ensure that the power supply is set to “external, M12 connected”. 

A supply from the PC would otherwise be superimposed on the 4...20 mA output signal and lead to an incorrect measur-

ing signal.

 Electrical connection | Power supply

Connecting the sensor

1.  Connect the sensor to the PC via the USB port.

2.  The graphic user interface now refreshes and shows the sensor (e.g. level switch 

NSL-M).

 MPI-200 user interface

2.

Advice

If the sensor is not displayed, check the power supply selection and change it 

if necessary.

M12 connector assignment (connector 1)

1:  +Auxiliary voltage

2:  -Auxiliary voltage 4...20 mA

3:  Data line for PC interface must 

not be wired

4:  Data line for PC interface must 

not be wired

Connection of programming adaptor MPI-200

1:  External power supply 

via M12-plug (optional)

2:  USB port for connection 

to PC incl. power supply 

if not supplied external

3:  Connection cable to 

NSL-sensor

1

3

2

Signal fl ow while parametrization

Negele-S

ensor

e. g. Level Sen

sor NSL-M

MPI-200

Negele

interface

(3)

PC

USB 

(2) 

PLC

mA (1)

Содержание MPI-200

Страница 1: ...her requirement CD drive for program installation Access rights Administrator rights for installation Installing the software 1 Insert the CD included with the MPI 200 into the CD drive 2 Double click...

Страница 2: ...external M12 connected A supply from the PC would otherwise be superimposed on the 4 20 mA output signal and lead to an incorrect measur ing signal Electrical connection Power supply Connecting the se...

Страница 3: ...t Reconnect Establishing a connection with a sensor reading in the parameter structure again manually Mode Mode setting Monitoring Process values and service information can be viewed but not changed...

Страница 4: ...ed e g 4 mA for a mA setpoint Save parameter The manually created setting is adopted and the display returns to the main menu Discard parameter The setting is not adopted and the display returns to th...

Страница 5: ...at can only be set to xed values By pressing the arrow buttons Only values that are greater than the cur rently displayed value are possible Only values less than the currently displayed value are pos...

Страница 6: ...out and saved After the language and the printer are selected in the option field 3 the process can be completed by clicking the OK button 1 2 3 Export function of the parameter list After the print m...

Страница 7: ...supply MPI 200 parameter set to PC Set the appropriate power supply Error message when the software is started Is NET 4 0 or higher installed on the PC Install NET from the supplied CD path NET4 0 Er...

Страница 8: ...te Note the cleaning information To avoid damage of the equipment use suitable trans port packaging only Transport storage Do not store outside Store in an area that is dry and dust free Do not expose...

Отзывы: