TABLE 1 

– DIAGNOSTIC CODES

Diagnostic 

Code

Failure Mode

Action

Reset

E1

Internal Humidity or 

Temperature Sensor 

Open or Shorted

1. 

Cycle power to clear error code�

2. 

If error code reoccurs replace User Interface, Part No� 5738�

Cycle Power

E3

Model A77 

Remote Control 

Communication Loss

1. 

Check connections between Model A77 and dehumidifier control board� Terminals should be fully 

inserted and secured in the control board and Model A77 control terminals�

2. 

If connections are correct and secure, turn off the dehumidifier and remove the Model A77� Use a 

short section of 4-wire cable to reconnect the Model A77 to the control board� Turn the dehumidifier 

back on and increase the dryness level setting on the Model A77� If the dehumidifier turns on, the 

problem is with the wiring between the dehumidifier and control�

3. 

If the dehumidifier does not turn on, call Technical Support�

Self-Correcting

E4

Insufficient Capacity

1. 

Check the frost sensor connection at the power board� Terminal should be fully seated on the power 

board pins�

2. 

Remove the side access panel and verify that the sensor is secured to the suction line�

3. 

If the sensor is connected and secured to the refrigeration line proceed to the next step� 

4. 

Reset the fault by cycling power to the dehumidifier�

5. 

Turn the humidity setting down (below room/home humidity level) to make a dehumidification call� 

6. 

Allow the fan and compressor to run for approximately 10-15 minutes and then enter diagnostic 

test mode by simultaneously pressing the UP ARROW and MODE buttons for 3 seconds� The LCD 

will display the temperature measured by the internal sensor while also displaying AIR SAMPLING 

and ON, the humidity measured by the internal sensor while also displaying %RH and ON, and the 

frost sensor temperature while also displaying ON� Scroll through these values and by using the UP/

DOWN arrow buttons� 

7. 

Record values and call Technical Support�

Cycle Power

E5

High Temperature 

Thermistor Failure

1. 

Check the high temperature sensor connection at the power board� Terminal should be fully seated 

on the power board pins�

2. 

Remove the side access panel and verify the sensor is not damaged and connected to the 

refrigeration line coming from the compressor�

3. 

If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part 

No� 5456 – contact Technical Support to confirm�

Cycle Power

E6

Low Temperature 

Thermistor Failure

1. 

Check the low temperature sensor connection at the power board�

2. 

Remove the side access panel and verify the sensor is not damaged and connected to the suction line�

3. 

If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part 

No� 5455 – contact Technical Support to confirm�

Self-Correcting

E7

Float Switch Open

1. 

Empty the condensate pan�

2. 

Check the float switch connection at the control board�

3. 

If not using a float switch, verify jumper is between float switch terminals on dehumidifier control board�

4. 

If the problem persists, replace the float switch�

Self-Correcting

E8

Inlet Air Temperature 

Out of 50°F – 104°F 

range or dew point 

below 40°F

1. 

Verify all ductwork is properly sealed�

2. 

If no signs of leak points, contact Technical Support�

Self-Correcting

TROUBLESHOOTING

Technical Support is available Monday through Friday, 7:00 a�m� to 5:00 p�m� CST, at (800) 972-3710� Use the guides on the following pages to identify 
and correct system faults� Contact Technical Support before replacing the unit or any components and for additional troubleshooting�

DIAGNOSTIC CODES

When an error occurs, the Diagnostic Code along with SERVICE REQUIRED will be displayed on the control 
screen� If a 5818 Alert Light is used, the light will turn on when an error occurs�

90-1854

12

Содержание A100F

Страница 1: ...IER FOR INSTALLATION 3 LOCATION CONSIDERATIONS 3 DRAIN INSTALLATION 4 Leveling 5 Condensate Pan Condensate Pump and Float Switch 5 MODEL A77 REMOTE CONTROL AND WIRING 6 Alternate External Controls 6 S...

Страница 2: ...property damage or injury Read instructions before installation service or maintenance 3 Do not use in pool applications Pool chemicals can damage the dehumidifier 4 Do not use solvents or cleaners on...

Страница 3: ...emoval of the side panel shown Allow sufficient space for service on this side of the unit Always install the dehumidifier in a condensate pan when locating in or over a finished space CLIP OFF PLASTI...

Страница 4: ...result in air lock NOTE PTFE thread seal tape is recommended for the threaded connection and hand tighten only If hard pipe is used PVC primer and cement is recommended for the slip fit connection Re...

Страница 5: ...the condensate pan remove the factory installed jumper wire between the Float Switch terminals on the control and wire the float switch to the dehumidifier as shown in FIGURE 4 Overflow safety switche...

Страница 6: ...rt up instructions The Model A77 will measure the relative humidity and turn the dehumidifier on and off to control the humidity level to the desired setting The humidity setting can be adjusted from...

Страница 7: ...r for the installed application Use the UP or DOWN buttons to select items and use MODE to switch to the next set up option To exit installer set up all options must be scrolled through using the MODE...

Страница 8: ...red the dehumidifier and all of the wired components will turn on and off during Installer Test Mode to demonstrate that all are properly operating Installer Test Mode lasts for four 4 minutes If the...

Страница 9: ...tting the blowers turn off and the display returns to showing the RH setting 4 The dehumidifier will sample again after the number of minutes selected during the Air Sampling portion of the System Set...

Страница 10: ...r 3 seconds to clear the service message 90 1854 MAINTENANCE CLEAN OR REPLACE THE AIR FILTER After initial installation the air filter should be checked and cleaned every 6 months The CLEAN FILTER ser...

Страница 11: ...p and gently lifting the cover up and out of the drain pan 6 Clean the drain insert with warm water and mild detergent solution REINSTALLING THE DRAIN INSERT 1 Reinstall the drain insert by inserting...

Страница 12: ...ture while also displaying ON Scroll through these values and by using the UP DOWN arrow buttons 7 Record values and call Technical Support Cycle Power E5 High Temperature Thermistor Failure 1 Check t...

Страница 13: ...s installed at the float switch terminals on the control board Coil frosting defrost Lack of or reduced airflow Check dehumidifier air filter and replace if necessary Check for blocked duct work Inlet...

Страница 14: ...Deh 5882 6 Fan 100pt Deh with 12MFD Capacitor 5886 7 Wire Harness Power Deh 5884 8 Sensor Low Temperature Deh 5455 No Part Description Part No 9 Sensor High Temperature Deh 5456 10 Capacitor Run 50 F...

Страница 15: ...IABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OTHER THAN DAMAGES FOR PERSONAL INJURIES RESULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLU...

Страница 16: ...anden com P O Box 1467 Madison WI 53701 1467 800 972 3710 F 608 257 4357 Printed in USA 2021 Anden A Quality brand from Research Products Corporation 10015567 B2209250A 1 21...

Отзывы: