WIRING INSTRUCTIONS 

Warning: 

Before making any connections, disconnect the electrical service (120 VAC) at the circuit breaker or fuse box. 
Dealing with 120V can be dangerous and lethal if not properly handled. Please have a qualified electrician do 
the wiring, connection, test, and maintenance. AND makes no representations as to the safety of the 
implementation. This process is the sole responsibility of the implementer, which should be a qualified 
electrician. All electrical connections must be made in accordance with local codes and/or ordinances. 

 

1.

 

Disconnect the CAT5 cable from the ZONEC2 PoE input to remove power from the device. 

2.

 

Connect the ZONEC2 into the slave clock circuit as shown in the figure above. 

a.

 

Connect t

he ZONEC2’s Output N.O. (Normally Open) and GND terminals to the 12VDC 

coil inputs on the panel mount relay. 

b.

 

Wire the N.O. terminal of the panel mount relay to the clock synchronization wire 
(sync), and wire the COM terminal of the relay to the hot side of the 120VAC. 

c.

 

Use parallel wiring to connect the synchronization signal to multiple slave clocks.   

3.

 

Set the Output Mode of the ZONEC2 to 

Sw DC 

as shown in the figure to the right.  

4.

 

Re-connect the CAT5 cable to the ZONEC2 PoE input to restore power to the ZONEC2.   

Installation is complete. Restore electrical power. Allow several hours for full clock 
synchronization to occur. 

Содержание ZONEC2

Страница 1: ...Version 2 1 2 25 2019 2019 ADVANCED NETWORK DEVICES 3820 NORTH VENTURA DR ARLINGTON HEIGHTS IL 60004 U S A ALL RIGHTS RESERVED Master Clock Operation for Legacy Slave Clocks ...

Страница 2: ...re warranted in accordance with the terms of the Warranty Statement accompanying each product However actual performance of each product is dependent upon factors such as system configuration customer data and operator control Since implementation by customers of each product may vary the suitability of specific product configurations and applications must be determined by the customer and is not ...

Страница 3: ...EC2 Form A Normally Open relay rated for 120VAC 30A with 12VDC coil e g TE Connectivity T9AP1D52 12 Consult with a qualified electrical contractor if selecting an alternate relay CONFIGURING THE AND DEVICE The ZONEC2 must be running firmware version 1 5 0001 or later You can configure the device to send sync pulses via its on board device settings or via a configuration file On board Settings Acce...

Страница 4: ... be made in accordance with local codes and or ordinances 1 Disconnect the CAT5 cable from the ZONEC2 PoE input to remove power from the device 2 Connect the ZONEC2 into the slave clock circuit as shown in the figure above a Connect the ZONEC2 s Output N O Normally Open and GND terminals to the 12VDC coil inputs on the panel mount relay b Wire the N O terminal of the panel mount relay to the clock...

Отзывы: