Master Clock Operation for Legacy Slave Clocks 

Содержание ZONEC2

Страница 1: ...Version 2 1 2 25 2019 2019 ADVANCED NETWORK DEVICES 3820 NORTH VENTURA DR ARLINGTON HEIGHTS IL 60004 U S A ALL RIGHTS RESERVED Master Clock Operation for Legacy Slave Clocks ...

Страница 2: ...re warranted in accordance with the terms of the Warranty Statement accompanying each product However actual performance of each product is dependent upon factors such as system configuration customer data and operator control Since implementation by customers of each product may vary the suitability of specific product configurations and applications must be determined by the customer and is not ...

Страница 3: ...EC2 Form A Normally Open relay rated for 120VAC 30A with 12VDC coil e g TE Connectivity T9AP1D52 12 Consult with a qualified electrical contractor if selecting an alternate relay CONFIGURING THE AND DEVICE The ZONEC2 must be running firmware version 1 5 0001 or later You can configure the device to send sync pulses via its on board device settings or via a configuration file On board Settings Acce...

Страница 4: ... be made in accordance with local codes and or ordinances 1 Disconnect the CAT5 cable from the ZONEC2 PoE input to remove power from the device 2 Connect the ZONEC2 into the slave clock circuit as shown in the figure above a Connect the ZONEC2 s Output N O Normally Open and GND terminals to the 12VDC coil inputs on the panel mount relay b Wire the N O terminal of the panel mount relay to the clock...