background image

 

2

2. Specifications 

AD-4329A-03 

RS-422 / 485 interface 

Transmission Asynchronous, 

half-duplex 

Baud rate 

600, 1200, 2400, 4800, 9600 bps 

Data bits 

7 bits 

Parity bits 

1 bit, Even 

Start bit 

1 bit 

Stop bit 

1 bit 

Code ASCII 

Terminator 

CR  LF  (CR: 0Dh,  LF: 0Ah) 

Number of indicators to be connected 

Max.10   

Terminal 

M3 compression terminal   

 

Circuit and Pin Connection 

 

 

 

 

 

 

 

 

 

Bit Format 

Signal 

RS-422 / RS-485 

SDA < SDB 

RDA < RDB 

SDA > SDB 

RDA > RDB 

 

 

Switching between RS-422 and RS-485 

Switching between RS-422 and RS-485 is performed by the function setting F-47. 

For details on the setting procedure, refer to the AD-4329A instruction manual. 

Item Parameter 

Description 

f-47

  

0

 

RS-422 (Factory setting) 

RS-422 / RS-485 

f-47

  

1

 

RS-485 

 

Data format and commands are the same as those of RS-232C. For details, refer to the description 

of RS-232C in the AD-4329A instruction manual.   

Содержание AD-4329A-03

Страница 1: ...duced transmitted transcribed or translated into any language in any form by any means without the written permission of A D Company Ltd The contents of this manual and the specifications of the instrument covered by this manual are subject to change for improvement without notice AD 4329A 03 RS 422 485 INTERFACE ...

Страница 2: ...to the rear panel from outside using the two screws removed in step 5 7 Connect the option cable to the option board connector and to the main board J3 connector using much care as to the connector direction 8 Insert the main board into the both main board guides Then the connector between the main board and the display board is re connected If the rear panel will not close completely retry step 8...

Страница 3: ...nal Circuit and Pin Connection Bit Format Signal RS 422 RS 485 1 SDA SDB RDA RDB 0 SDA SDB RDA RDB Switching between RS 422 and RS 485 Switching between RS 422 and RS 485 is performed by the function setting F 47 For details on the setting procedure refer to the AD 4329A instruction manual Item Parameter Description f 47 0 RS 422 Factory setting RS 422 RS 485 f 47 1 RS 485 Data format and commands...

Страница 4: ...built into the host computer Connect the terminating resistor only to the indictor which is furthest from the host computer RDA RDB SDA SDB SG RDA RDB SDA SDB TRM SG RDA RDB SDA SDB TRM SG RDA RDB SDA SDB TRM SG A B SG RDA RDB SDA SDB TRM SG RDA RDB SDA SDB TRM SG RDA RDB SDA SDB TRM SG Host computer AD 4329A Address 1 AD 4329A Address 2 AD 4329A Address 10 Host computer AD 4329A Address 1 AD 4329...