ANATEL Novus RHT-Air Скачать руководство пользователя страница 5

NOVUS AUTOMATION 

5/10 

6

 

CONFIGURATION / OPERATION 

DigiConfig

 is a Windows software used for configuring 

RHT-Air

. To install 

it, please run the file “

DigiConfigSetup.exe

”, available in our website 

www.novusautomation.com

DigiConfig

  comes with an unabridged help tutorial, containing all the 

necessary information for you to use it. If you want to use help tutorial, start 

the application, and select the 

Help

 menu or press F1. 

Check our website for get the 

DigiConfig

 installer and the additional manual 

guides. 
Users will receive the fully calibrated adjustment-free device. The original 

configuration is shown below: 

Addr

 (Communication address) = 246 

Time

 

(Update interval) = 60 s 

To configure it for the first time, it is necessary to remove the front cover and 

connect it to a computer through a mini-B USB cable. The initial configurations 

for wireless are described as follows: 

PAN ID (Network Identifier) = 22350 (0x574E) 
RF Power (Power Level) = 0 dBm 

6.1

 

RHT-Air SCREENS 

Indication screen of the values measured in the device: 

 

1ª Screen: 

Main

 

To  configure the communication parameters, you should press the button 

  (for about 5 seconds) until it starts to blink. Release it and press it 

again to expand it. When the expected value appears, release the button, 

and wait until the screen stops blinking (for about 10 seconds). If you want to 

move on to the following screens, press the button 

Modbus Address

 configuration screen: Sets the address of the module on 

the Modbus network. Values between 1 and 246. 

 

2ª Screen: 

Modbus Address 

Time

 configuration screen: Sets the update interval in seconds.  

 

3ª Screen: 

Update interval 

Mode

 configuration screen: Sets the indication mode. 

 

4ª Screen: 

Indication mode 

CODE 

DESCRIPTION 

Indicates temperature and relative humidity. 

Indicates temperature and dew point. 

Indicates relative humidity and dew point. 

Indicates only temperature. 

Unit

 configuration screen: Sets which temperature unit should be used (°C 

or °F).

    

 

5ª Screen: 

Unit 

 
 

Display screens only for measured values on the device: 

 

6ª Screen: 

Temperature

 

 

7ª Screen: 

Relative humidity

 

 

8ª Screen: 

Dew point 

7

 

WIRELESS COMMUNICATION 

RHT-Air

  has an IEEE 802.15.4 wireless communication to connect to 

AirGates-Modbus

 that has its firmware updated to a version more recent 

than V1.23. The first 

RHT-Air

 configuration must be performed via the USB 

interface through the 

DigiConfig

 

software. In it, the necessary parameters 

for communication with 

AirGates

 network should be set. After the first time it 

is configured and matched with a 

AirGate-Modbus

RHT-Air

 will operate as 

a Modbus RTU slave.  From this moment on, all its resources can be 

accessed by reading its registers anywhere in any Modbus RTU network. 

Some settings can be made via the programming button 

In this section you will find the necessary information to carry out the data 

readings without the use of the 

DigiConfig

 software. To ensure the correct 

device configuration, use the 

DigiConfig

  software. Once configured, the 

data of its inputs can be accessed by any other software with Modbus RTU 

communication capability. 

7.1  MODBUS COMMANDS 

The following Modbus RTU commands (functions) are implemented. For 

further information on each one of these functions and on the Modbus 

protocol in general, go t

www.modbus.org

READ HOLDING REGISTERS – 0x03 

This  function can be used to read a value of one or up to 42 retentive 

registers, as per the 

Retentive Registers Table

.  

WRITE HOLDING REGISTERS – 0x06 

This function can be used to write in a retentive register, as per the 

Retentive Registers Table

7.2  DESCRIPTION OF SOME REGISTERS 

Once 

RHT-Air

 meets an 

AirGate-Modbus

 and is matched, this 

AirGate

 will be 

last published by 

RHT-Air

. Therefore, when the Master of the Modbus network 

requires that the 

RH-Air

 address be read, the response is sent immediately 

and the expiration of this publication can be checked through register 30, which 

shows how long it has been since the last publication. 

REGISTER 6 – PAN ID 

Common identifier for each IEEE 802.15.4 wireless network. All devices on 

the same network (

AirGates-Modbus

  and 

RHTs-Air

) must be configured 

with the same 

PAN ID

REGISTER 7 – ENCRYPTION 

This register should be used to enable or disable the use of encryption. If it 

is enabled, the encryption key should be the same used for all  device 

configured with the same 

PAN ID

Содержание Novus RHT-Air

Страница 1: ...NOVUS AUTOMATION 1 10 RHT Air WIRELESS DEVICE FOR TEMPERATURE RELATIVE HUMIDITY AND DEW POINT INSTRUCTIONS MANUAL V2 0x A...

Страница 2: ...212 F Relative Humidity RH 0 0 to 100 0 RH No condensation Dew Point 40 C and 100 C 40 F to 212 F Measurements Accuracy See Figure 3 Note It is possible to perform an Offset adjustment using the DigiC...

Страница 3: ...one through USB interface Remove the four set screws of the front panel of the RHT Air device taking the necessary precaution not to apply force on the internal connector of the electronic circuit Fig...

Страница 4: ...register When it reaches values below 3 3 V a battery change must be scheduled this register may present a measurement error of up to 5 Note Even when the power is below 100 the device will operate n...

Страница 5: ...y 8 Screen Dew point 7 WIRELESS COMMUNICATION RHT Air has an IEEE 802 15 4 wireless communication to connect to AirGates Modbus that has its firmware updated to a version more recent than V1 23 The fi...

Страница 6: ...z 21 2455 MHz 22 2460 MHz 23 2465 MHz 24 2470 MHz 25 2475 MHz REGISTER 28 LINK QUALITY INDICATOR It serves to inform the quality of the reception link of the connection between the device and the AirG...

Страница 7: ...e Modbus network This address identifies the device on the Modbus network Its configuration may range from 1 and 247 There cannot be more than one piece of device with the same address on the same net...

Страница 8: ...rror value 9999 9999 R W 39 Temperature value C or F 400 1000 R 40 Relative humidity value 0 1000 R 41 Dew point value C or F 400 800 R For the abovementioned table ranges one decimal place should be...

Страница 9: ...the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that...

Страница 10: ...NOVUS AUTOMATION 10 10 11 WARRANTY Warranty conditions are available on our website www novusautomation com warranty...

Отзывы: