All connections should be made inside an appropriate junction box. The maximum current 
draw from the 110 VAC supply is 14.6 amps, so a 20 amp circuit breaker should be used in the 
circuit panel and for a 220 VAC supply, 7.3 amps is the maximum current draw, so a 10 amp 
circuit breaker should be used in the circuit panel to feed power to the PWS1000R. 

A ground stud is provided to bond the chassis to local ground to reduce or eliminate EMI.

OUTPUT CONNECTIONS

Two Positive output terminals and two Negative output terminals are provided. Connect only 
one wire to each terminal. Ensure that the total average load connected does not exceed the 
continuous current rating of the unit. 

For 12Vdc Model Only!

For 12 Vdc models only, the output terminals must be connected as shown below if the load current is 
greater than 50 amps!

OUTPUT 1

OUTPUT 2

LOAD

MOUNTING

Mount the unit in a DRY location. Allow at least 4 inches of clearance around it for adequate 
cooling.

POWER CONNECTION

The unit is supplied with a 5 foot power cable. This should normally be adequate to connect to 
a source of power. If you must extend the power cable be sure to use a 3 conductor grounded 
type extension cable. For hard wiring to a source of power, cut off the plug, and strip the wires 
as necessary. The wire colours are

Installation

110 VAC

220 VAC

Brown - AC Hot

Brown - AC Hot / Phase 1

Blue - AC Neutral

Blue - AC Neutral / Phase 2

Green - Ground

Green/Yellow - Ground

Содержание PWS1000R series

Страница 1: ...kmount Power Supply 8128 River Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers In...

Страница 2: ...Copyright 2005 2016 Analytic Systems Ware 1993 Ltd Revised May 20 2016...

Страница 3: ...roperly installed and grounded in accordance with al local codes and ordinances DANGER Never alter AC cord or plug provided if it will not fit outlet have proper cord installed by a qualified electric...

Страница 4: ...protects devices connected to the converter The PWS1000R Series Rack Mount Voltage Converter supplies either 12 24 or 48 VDC from a 12 24 or 48 VDC power source Other input or output voltages up to 72...

Страница 5: ...g C maximum output Isolation Input Output Input Case 1500 Vdc Output Case 500 VDC 1500Vdc 48 V Out Dimensions 14 5 x 10 2 x 5 5 in 36 8 x 25 9 x 14 0 cm Clearance 1 Inch 2 5 cm all around Material Mar...

Страница 6: ...connected does not exceed the continuous current rating of the unit For 12Vdc Model Only For 12 Vdc models only the output terminals must be connected as shown below if the load current is greater tha...

Страница 7: ...the diodes are NOT present the terminals will measure the static load resistance Value depends on the output voltage of the unit Assuming the output isolation diodes are present connect one 4 foot pi...

Страница 8: ...DC If you wish to adjust this voltage reach in with a very small flat blade screwdriver to rotate the potentiometer Clockwise increases the output voltage and counter clockwise decreases it Meters The...

Страница 9: ...ceeds the maximum output current rating causing the output voltage to drop to maintain the current at the maximum level The input voltage is not high enough for unit to operate LOW INPUT Indicates tha...

Страница 10: ...10 Page intentionally left blank...

Страница 11: ...ing will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed...

Страница 12: ...Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 and AS9100 Registered Company Battery Chargers Inverters Power Supplies Voltage...

Отзывы: