BATTERY LO VOLTAGE
NO BATTERY
I/P
POL
TEMP
25
DEV
CH
75
SVC
FLT
LO V
BAT
50
EQ
PS
I/P
POL
TEMP
25
DEV
CH
75
SVC
FLT
LO V
BAT
50
EQ
PS
No Battery Detected
The charger has detected that no battery is connected.
Connect a battery to the unit to clear this fault.
If a battery IS connected and you see this fault, this
usually means the battery is completely discharged.
Try switching the unit to Power Supply mode for a few
minutes and then back to Charger mode to see if it will
return the battery to life. If it doesn’t, the battery is defec-
tive and will have to be replaced.
Battery Low Voltage Indication
If the battery is seriously discharged, and the charger
voltage drops below 85% of nominal (ie. 10V for a 12V
charger), the charger will show this display until the
battery voltage exceeds 85% of nominal.
BATTERY FAILED
I/P
POL
TEMP
25
DEV
CH
75
SVC
FLT
LO V
BAT
50
EQ
PS
Battery Fail Indication
The charger has detected the connected battery is defec-
tive and will not accept a charge, the charger will stop
attempting to charge the battery. Replace the battery and
cycle power to the unit using the Power Button to reset
this condition.
CHARGER FAILED
I/P
POL
TEMP
25
DEV
CH
75
SVC
FLT
LO V
BAT
50
EQ
PS
Charger Failure Indication
The microprocessor has detected a condition that prevents
the charger from operating. Try disconnecting the Input
power and re-connecting it. If this does not clear the fault,
the cause is likely an internal component failure and the
charger will have to be returned for service
FAULT INDICATORS
BLINKING