Страница 1: ...iver Way Delta B C V4G 1K5 Canada T 604 946 9981 F 604 946 9983 TF 800 668 3884 US CANADA www analyticsystems com An ISO9001 Registered Company Battery Chargers Inverters Power Supplies Voltage Converters BCA150 AC SOURCE BATTERY CHARGER ...

Страница 2: ...ode and damage battery charger 6 Never allow battery acid to drip on the battery charger BATTERY SAFETY 1 WARNING RISK OF EXPLOSIVE GASES i WORKING IN VICINITY OF A LEAD ACID BATTERY IS DANGEROUS BATTERIES GENERATE EXPLOSIVE GASES DURING NORMAL BATTERY OPERATION FOR THIS REASON IT IS OF UTMOST IMPORTANCE THAT EACH TIME BEFORE SERVICING EQUIPMENT IN THE VICINITY OF THE BATTERY YOU READ THIS USER GU...

Страница 3: ...oper connection can result in the risk of electric shock i NEVER smoke or allow a spark or flame in the vicinity of a battery ii Be extra cautious to reduce risk of dropping a metal tool onto battery It might spark or short circuit the battery or other electrical part that may cause a fire or explosion iii Remove personal metal items such as rings bracelets necklaces and watches when working with ...

Страница 4: ...uct Warnings and Advisories Table of Contents Introduction Box Contents Main Parts Operation Two Stage Charging Installation Troubleshooting Specifications Warranty Revised April 11 2018 Copyright 2005 2017 Analytic Systems Ware 1993 Ltd ...

Страница 5: ...5 Page intentionally left blank ...

Страница 6: ... the absence of a battery the BCA150 can also function as a power supply up to its continuous current rating Designed for maximum safety unit s reliability features include spark free battery connections reverse battery connection protection over temperature shutdown with automatic recover and both input and output fuses Additional features include a drip shield for wall mounting and visual indica...

Страница 7: ... 6 3mm 3 DC Output Connections 2 sets Phoenix VDFK4 Terminal Blocks Red and Black 4 Chassis Grounding Screw 2 4 3 Main Parts Front Panel Top Panel 1 Lighted Power Switch 2 Power Indicator LED 3 Drip Shield 4 Integrated Digital Voltmeter 5 Load Indicator LEDs Output 1 2 2 1 3 5 1 4 ...

Страница 8: ...ic charging needs To adjust the charging voltage 1 Using a small flat blade screwdriver rotate the Output Voltage Adjust potentiometer Rotate clockwise to increase the output voltage 2 Rotate it counterclockwise to decrease the output voltage 3 You can check the charging voltage using the integrated digital voltmeter LED Indicators The BCA150 features several indicator LEDs on its top panel to dis...

Страница 9: ...ies Then during the float stage the battery is held at the float voltage the current reduces as necessary to maintain it at this voltage The battery can be left connected to the charger indefi nitely which will maintain it A two stage charger is recommended in most instances over a three stage charger since it is the most versatile The battery is also subjected to lower voltages than in three stag...

Страница 10: ...nt see Specifications for more information These connections are wired as follows RED Positive Battery Terminal BLACK Negative Battery Terminal These connections can be used to charge up to two battery banks simultaneously If charging a single battery connect the positive terminal of that battery to both positive DC outputs this will reduce strain on the connection AC Input Connection This unit is...

Страница 11: ...the 2 screws securing the drip shield to the top panel 3 Slide the top panel free from the bottom panel 4 Locate the blown fuses found on the back front panel circuit board They are directly behind the DC Output connections 5 Replace the fuses with suitable replacements For more information on the make and model of the output fuses see Specifications 6 Return the top panel to its original position...

Страница 12: ...ver current by conventional means Usually the input fuses blowing means there is an internal component failure and the unit must be returned for repair Issue The unit keeps turning OFF Check Check the temperature of the unit If the unit is running above its operating temperature range its thermal derating may cause it to turn OFF If the unit feels significantly hot improve the air circulation arou...

Страница 13: ...4 cm Wide x 2 2 in 5 6 cm High Clearance 1 0 in 2 5 cm all around Weight 3 6 lb 1 6 kg Mounting Wall Mount with Drip Shield Material Finish Marine Grade Black Powdered Aluminum with 18 8 Stainless Fasteners Connections AC Input 3 pin IEC320 AC Inlet 6 3mm Tab Flange Mount DC Output 2x Phoenix VDFK4 Terminal Blocks Red and Black Environmental and Safety Operating Temperature Range 25 C to 40 C maxi...

Страница 14: ...14 Page intentionally left blank ...

Страница 15: ...ng will incur additional charges and are the responsibility of the Purchaser 6 Analytic Systems reserves the right to void the warranty if a Labels identification marks or serial numbers are removed or altered in any way b Our invoice is unpaid c The defect is the result of misuse neglect improper installation environmental conditions non autho rized repair alteration or accident 7 No refund of th...