Electrical Performance 

Electrical 

Specification  

MODEL 

Item 

AMV OND1000-24-C1 

AMV OND1000-48-C1 

Voltage 

24VDC 

48 VDC 

Input Over-Voltage 

Protection 

30-34 VDC 

60-68 VDC 

Input Under-Voltage 

Protection 

18-22 VDC 

36-44 VDC 

Voltage Range 

18-34 VDC 

36-68 VDC 

Input 

Characteristics 

No Load Current  

0.6 A 

0.35 A  

Continuous Output Power 

1000 W  

Maximum output Power 

(3Min) 

1150 W  

Surge Power 

2000 W  

Frequency 

50 / 60 Hz +/- 0.05  

Output Voltage 

194-246 VAC (User-selectable) 

Efficiency (Full Load) 

90% 

91% 

Short -Circuit Protection 

Yes, Ipk 

Output  

Characteristics 

Output Waveform 

Pure Sine Wave (THD < 2%) 

LCD Panel 

2 Lines LCD Panel with keypad for navigation 

LED Indicator 

Red/Orange/Green LED 

Dry Contact Terminal 

By a relay 

Signal and Control 

Remote Control Terminal 

Controls the inverter ON / OFF operation 

Input Protection 

Over/Under Voltage, Reverse Polarity (Internal Fuse) 

AC Output Protection 

Short -circuit, Overload 

AC Input Protection 

6Amp Circuit Breaker 

Protection 

Temperature protection 

Shutdown (Internal temperature S65° C) 

Relay Specification 

12 Amp/250 VAC 

Bypass relay 

On Line/Off Line (Haphazard, Normal, Exacting) selectable 

From AC bypass mode(0ff-iine Mode): S9mS 

From DC to AC inverter mode(0n-line Mode):g7mS 

Transfer Relay 

Switching Time 

 

Full Load 

0° C - 50° C 

Operating 

Temperature  

Storage 

-30° C~70° C 

Failure Indication 

Buzzer alarm and dry contact  

Switches On when 

Temperature = 55° C or Load=30 

Fan Operation and 

Indicator 

Switches Off when 

Temperature =45° C and Load=20 

Size (WXHXD) 

19"x1.71"x13.6"(482.6mmX43.5mmX345mm) 

Mechanical 

Specification 

Weight  

5.8 Kgs (12.7 Lbs) 

Safety Standards 

Meets UL 60950    Meets EN60+950-1 
 

Safety and EMI/ EMC 

EMC standards 

FCC CLASS B  EN55022 1998+A1 2000+A2 2003 CLASS B 
                    EN55024: 1997+A1: 2001+a2 :2003 
                    EN61000-3-2: 2006 Class A 
                    EN61000-3-3: 11995+A1:2001 
 

 

Содержание OND1000-X-C1

Страница 1: ...KW Pure Sine Wave Power Inverter User s Manual AMV OND1000 X C1 AMV ELECTR NICA SL C NAVA N 7 BAJO 33207 GIJON ASTURIAS TFNO 985319171 FAX 985346795 EMAIL amv amvelectronica com www amvelectronica com...

Страница 2: ...12 3 3 Maintenance 12 4 Operation 12 4 1 Connecting the Input Power 12 4 2 Connecting the Loads 12 4 3 Inverter Operation 13 4 4 Protection Features 13 5 Front LCD Panel Display and Setup 13 5 1 LCD...

Страница 3: ...t protection 1 1 4 The following precautions should be taken when working on the inverter Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves and boots 1 2...

Страница 4: ...ighly reliable DC AC inverter system designed with advanced power electronic and microprocessor technology offering the following features The inverter is equipped with a self diagnosis microprocessor...

Страница 5: ...y AC output voltage is provided in one of the two following modes 1 From DC to AC Inverter Mode On line Mode 2 From AC Input Bypass Mode Off line Mode Either mode is front panel programmable In the fi...

Страница 6: ...ls the inverter ON OFF operation Input Protection Over Under Voltage Reverse Polarity Internal Fuse AC Output Protection Short circuit Overload AC Input Protection 6Amp Circuit Breaker Protection Temp...

Страница 7: ...KER CHASSIS GROUND WARNING POS NEG REVERSE POLARITY WILL DAMAGE UNIT O N OFF REMOTE Inverter Ordering Information Model Number Input Voltage Output Voltage Nominal Output Voltage Range Frequency Range...

Страница 8: ...aker protects the unit from overload When an overload condition occurs the circuit breaker trips and disconnects the AC grid power input To reset it push the circuit breaker button The cause of trippi...

Страница 9: ...AWG 12 14 Note Please double check and review all the connections to ensure that the wires are connected to the correct terminals and that the connections are tight 3 1 3 AC output socket 110VAC NEMA...

Страница 10: ...D ON INV ON OFF INV OFF ENB DC POWER NOTE At one time only one remote function should used to control the inverter The maximum voltage value is the same as input DC voltage Dry Contact Terminals Dry c...

Страница 11: ...rrents in case of short circuit In case there is a short circuit in the cable run between the batteries and the input terminals of the inverter it will result in overheating melting of the cables and...

Страница 12: ...and keep the cable length short which is a maximum of 3 6 feet INLINE FUSE NEGATIVE POSITIVE WARNING The recommended inline fuse should be installed as close to the battery positive terminal as possib...

Страница 13: ...Make sure that the fan vents are not blocked 3 3 2 Use a vacuum cleaner to remove any dust from the fan area 3 3 3 When cleaning the case or front panel use a soft dry cloth only If the case or front...

Страница 14: ...OFF position THE inverter stops and all the lights that are on will go off 4 4 Protections Features DC Input VDC Over Temperature Protection Over Voltage Under Voltage INTERIOR HEAT SINK Model Shut d...

Страница 15: ...ays DC AC inverter status DC AC Inverter LED Status Power OK GREEN Power not good RED BYPASS Displays Transfer Switch status BYPASS LED Status AC OUTPUT LOAD ORANGE AC INPUT From DC AC inverter On lin...

Страница 16: ...through the menus Function Page Down You can use the Page Down button to scroll through the menus Function Enter Setup Menu Press the button longer than 2 seconds The inverter will change to Setup Me...

Страница 17: ...ARM Vi XX X Vo XXX FQ XX X Io X X FQ XX X Io X X Vi XX X Vo XXX Undervoltage Alert 1Sec OR OR Alert Overload Alert Fan Failure 5 3 Setup Menu Operation and Instructions Entering Setup Menu Press Butto...

Страница 18: ...st Setting Value LCD Auto off 120S RS232 Baudrate 4800 Buzzer Setting MSG Alert SHDN Alert Setting Alert SHDN OVP Setting 32 00V 30 00V OVO Recovery 20 00V UVP Setting 25 00V UVP Recovery 21 00V UV Al...

Страница 19: ...V Model Model SETTING VALUE RANGE 24 V 30 VDC 34 VDC 48 V 60 VDC 68 VDC 7 OVP Recovery When the DC input voltage is higher than the OVP setting the inverter shuts down Once the input voltage falls bel...

Страница 20: ...udible warning 5 3 3 O P Parameters 11 O P Voltage Set the inverter output voltage Default 110 VAC for 110 V Model 230 VAC for 220 V Model Model SETTING VALUE RANGE 110 V 97 VAC 123 VAC 220 V 194 VAC...

Страница 21: ...sfer relay will be ON if AC input Grid power is available The DC AC inverter will remain synchronized and Phase with the incoming AC power Grid The relay will NOT switch off if the grid frequency is b...

Страница 22: ...open close See details in Section 3 1 6 Default 100 Setting range 50 110 6 RS 232 Communication and Operation 6 1 Operation of RS 232 Serial Port 6 1 1 This unit uses a standard 9 Pole D connector an...

Страница 23: ...ved command AND OR data if it is correct Irrespective of whether the command is accepted or not the unit will always send back a response signal to the computer and set DTR to ready for receiving more...

Страница 24: ...en 4 Command to query the Output Current Format AMP After Enter the unit s Output Current appears on the PC screen 5 Command to query the Input Battery Voltage Format BAT After Enter the unit s Input...

Страница 25: ...rmat SETT value After Enter the new value of the Function is set Choose the value of the function as follows FUNC 0 LCD Contrast Setting Menu SETT value LCD Contrast 0 100 FUNC 1 LCD Auto off Setting...

Страница 26: ...FUNC 7 OVP Recovery Setting Menu SETT value Model AMV 28 32 OND1000 24 C1 AMV OVP Recovery 56 64 OND1000 48 C1 FUNC 8 UVP Setting Setting Menu SETT value Model AMV 18 22 OND1000 24 C1 AMV UVP Setting...

Страница 27: ...lue MODE 0 ON LINE 1 Haphazard OFF LINE 2 Normal OFF LINE Bypass Relay 3 Exacting OFF LINE FUNC 15 Overload Alarm Setting Menu SETT value Overload Alarm 50 110 7 Information 7 1 Troubleshooting Proble...

Страница 28: ...e Reduce input voltage c LCD Panel Display UVP Shutdown Low input voltage UVP Recharge battery Check connections and cables d LCD Panel Display OTP shutdown Thermal shutdown OTP Improve ventilation Ma...

Страница 29: ...AMENTO RESPONSABLE TELEFONO e MAIL Comercial y Ventas Gracia Nomparte 985319171 Ext 10 gracia amvelectronica com Ingenier a V ctor Vi a 985319171 Ext 18 Producci n Jenaro Blanco 985319171 Ext 13 compr...

Страница 30: ...MV ELECTR NICA SALEN DE NUESTROS TALLERES AJUSTADOS NUMERADOS Y CON DOCUMENTACI N T CNICA SIENDO LA GARANTIA TOTAL DE 2 A OS LA GARANT A CUBRE LAS SITUACIONES DE DA O INTR NSECO Y NO LAS PROVOCADAS PO...

Отзывы: