23
AMV OND1000-X-C1
6-3-2. Command format:
This unit supports the following command format.
There should always be a CR (0DH) and a LF (0AH) appended to the
command while sending the command to this unit.
1). Command to switch the Power ON/OFF:
Format: Power <value>
Example: A space (ASCII code 20H) is needed between Power and
<value>.
<value> can be one of the following.
“0”: Power off
“1”: Power on
2). Command to query the Output Frequency:
Format: FRQ?
After “Enter”, the unit’s “Output Frequency” appears on the PC screen.
3). Command to query the Output Voltage:
Format: VOL?
After “Enter”, the unit’s “Output Voltage” appears on the PC screen.
4). Command to query the Output Current:
Format: AMP?
After “Enter”, the unit’s “Output Current” appears on the PC screen.
5). Command to query the Input Battery Voltage:
Format: BAT?
After “Enter”, the unit’s “Input Voltage” appears on the PC screen.
6-3-3. Command for accessing Setup Menus and adjusting values:
1). Select the Setup Menus with the help of Function Codes:
Format: FUNC <Function Code>
After “Enter”, the Setup Menu for the Function Code will be called.
The <Function Code>= 0~17, as follows:
<Function Code>
Setting Menu
<Function Code>
Setting Menus
0
LCD Contrast
9
UVP Recovery
1
LCD Auto-off
10
UV Alarm
2
RS232 Baud-rate
11
O/P Voltage
3
Buzzer Setting
12
O/P Frequency
4
Alert Setting
13
Sync Frequency
5
NOT USED
14
Bypass Relay
6
OVP Setting
15
Overload Alarm
7
OVP Recovery
16
NOT USED
8
UVP Setting
17
NOT USED