3-6. AC Safety Grounding

 

The AC output ground wire should go to the grounding point for your loads 
( for example, a distribution panel ground bus ). 

3-6-1. Neutral Grounding (GFCI’S)

 

3-6-1-1. 

120V models

The neutral conductor of the AC output circuit 

of the Inverter is automatically connected to the safety 

ground during inverter operation.    In accordance with the 
National Electrical Code requirements that separately derived 
AC sources (such as inverter and generators) have their 
neutral conductors tied to ground in the same way that the 
neutral conductor from the utility is tied to ground at the AC 
breaker panel.    For models configured with a transfer relay, 
while AC utility power is presenting and the Inverter is in 
bypass mode, this connection (neutral of the Inverter’s AC 
output to input safety ground) is not present so that the utility 

neutral is only connected to ground at your breaker panel, 

as required. 

3-6-1-2. 

230V models

There is no connection made inverter interior 

between either the line or neutral conductor to the safety 
ground. 

 
 
 
 
 
 
 

WARNING! 

Risk of electronic shock.  Use only Pass and Seymour, type 
2091-W or 2094-W, ground – fault circuit-interrupter 
receptacles.  Others may fail in operating the inverter when 
connecting to the inverter’s equipment.   

 
 
 
 
 
 
 

 

 

16

Содержание SK3000 Series

Страница 1: ......

Страница 2: ... 2 2 2 Electrical Performance 3 2 3 Mechanical Drawings 4 3 Introduction 5 3 1 Front Panel Operations 5 9 3 2 Rear Panel Operations 10 11 3 3 Protections Features 11 3 4 Installation 12 3 5 Making DC Wiring Connections 13 15 3 6 AC Safety Grounding 16 17 3 7 Inverter Operation 17 4 Troubleshooting guide 18 5 Maintenance 19 6 Warranty 19 7 Appendices ...

Страница 3: ...e materials or in locations which require ignition protected equipment This includes any space containing gasoline powered machinery fuel tanks or joints fittings or other connection between components of the fuel system 1 2 Precautions When Working with Batteries 1 2 1 If battery acid contacts skin or clothing wash immediately with soap and water If acid enters eye immediately flood eye with runn...

Страница 4: ...arm Input over voltage Over temperature 2 1 Application 2 1 1 Power tools circular saws drills grinders sanders buffers weed and hedge trimmers air compressors 2 1 2 Office equipment computers printers monitors facsimile machines scanner 2 1 3 Household items vacuum cleaners fans fluorescent and incandescent lights shavers sewing machines 2 1 4 Kitchen appliances microwave ovens refrigerators and ...

Страница 5: ...A 0 19A 0 55A 0 35A 0 19A Input Voltage Regulation 10 5 15 VDC 21 0 30 VDC 42 60 VDC 10 5 15 VDC 21 0 30 VDC 42 60 VDC Input Level Indicator Load Level Indicator Red Orange Green LED Failure Indicator Red LED Protection Overload Short Circuit Reverse Polarity Fuse Over Under Input Voltage Over Temperature Remote Control Unit CR 6 CR 8 Optional Safety UL458 EN60950 EMC FCC Class A EN55022 1997 EN55...

Страница 6: ...2 3 Mechanical Drawings I 0 Pure Sine Wave Power Inverter 3000W 4 ...

Страница 7: ...dvanced line of mobile AC power systems available To get the most out of the power inverter it must be installed and used properly Please read the instructions in this manual before installation and operation this model 3 1 Front Panel Operations 3 1 1 Front view 0 I I 0 5 ...

Страница 8: ...ges LED Status DC 12V DC 24V DC 48V RED Blink slow 10 5 10 9 21 0 21 8 42 0 43 6 RED 10 9 11 3 21 8 22 6 43 6 45 2 ORANGE 11 3 12 0 22 6 24 0 45 2 48 0 GREEN 12 0 14 0 24 0 28 0 48 0 56 0 ORANGE Blink 14 0 14 7 28 0 29 4 56 0 58 8 OVER RED BLINK 14 7q 29 4q 58 8q 3 1 4 Load Level Display AC Loads Watts LED Status Load Condition DARK 0 150W GREEN 150W 990W ORANGE 990W 2250W RED 2250W 2880W RED BLIN...

Страница 9: ...dvanced line of mobile AC power systems available To get the most out of the power inverter it must be installed and used properly Please read the instructions in this manual before installation and operation this model 3 1 Front Panel Operations 3 1 1 Front view 0 I I 0 5 ...

Страница 10: ...ting at 40W a 40W or greater load will wake up the inverter and the load will operate normally Any load less than 40W will not operate and the inverter will remain in power save made Power saving S1 S2 S3 DISABLE OFF OFF OFF 40W ON OFF OFF 80W OFF ON OFF 100W ON ON OFF 120W OFF OFF ON 160W ON OFF ON 180W OFF ON ON 220W ON ON ON 8 ...

Страница 11: ...a New Zealand IEC 2 Universal United Kingldom North America GFCI NEMA 5 20R Continental European WARNING Never connect the inverter s output to the AC distribution grid such as your household AC wall outlet It will damage the inverter 9 ...

Страница 12: ...E 3 2 2 Fan Ventilation Do not obstruct allow at least 1 inch for proper air flow 3 2 3 DC Input Terminals Connect to 12V 24V 48V battery or the other power sources is positive is negative Reverse polarity connection will blow internal fuse and may damage inverter permanently DC Input Voltage Model Minimum Maximum SK3000 112 SK3000 212 10 5 15 0 SK3000 124 SK3000 224 21 0 30 0 SK3000 148 SK3000 24...

Страница 13: ...azard 3 3 Protections Features DC Input VDC Over Temperature Protection Over Voltage Under Voltage INTERIOR HEAT SINK Model Shut down Restart Under Voltage Alarm Shut down Restart Shut down Restart Shut down Restart SK3000 112 SK3000 212 15 3 14 2 11 0 10 5 12 5 SK3000 124 SK3000 224 30 6 28 4 22 0 21 0 25 0 SK3000 148 SK3000 248 61 2 56 8 44 0 42 0 50 0 70 45 90 60 11 ...

Страница 14: ...not install the Inverter in a dusty environments where are dust wood particles or other filings shavings are present These dust can be pulled into the unit when the cooling fan is operating 3 4 6 Close to batteries Avoid excessive cable lengths but do not install the Inverter in the same compartment as batteries Use the recommended wire lengths and sizes see section 3 4 Also do not mount the Inver...

Страница 15: ...e warnings frequently and shutdowns UVP warning presents due to DC voltage drop across the cables from the inverter to the batteries The longer or narrower the cables the greater the voltage drop Increasing your DC cable size will help improve the situation Following cable recommendations for the best performance of inverter Apply both 120V and 230V versions Model No Wire AWG Inline Fuse SK3000 11...

Страница 16: ...r and battery may cause damage to the inverter and will void warranty Also use only high quality copper wire and keep cable length short a maximum of 3 6 feet DC INPUT WARNING REVERSE POLARITY WILL DAMAGE UNIT SHOCK HAZARD DO NOT OPEN NO USER SERVICEABLE PARTS INSIDE POS NEG REMOTE PORT CHASSIS GROUND INLINE FUSE SK3000 14 ...

Страница 17: ...minals on the rear panel of the inverter The red terminal is positive and black terminal is negative Insert the cables into the terminals and tighten screw to clamp the wires securely CAUTION Reverse polarity connection will blow a fuse in inverter and may permanently damage the inverter Damage caused by reverse polarity connection is not covered by warranty 15 ...

Страница 18: ... the neutral conductor from the utility is tied to ground at the AC breaker panel For models configured with a transfer relay while AC utility power is presenting and the Inverter is in bypass mode this connection neutral of the Inverter s AC output to input safety ground is not present so that the utility neutral is only connected to ground at your breaker panel as required 3 6 1 2 230V models Th...

Страница 19: ...he power inverter is now ready to deliver AC power to your loads If there is several loads use turn them on separately after the inverter has been ON in order to prevent the OVP present caused by the surge power 3 7 1 Set the power switch to the ON position and the buzzer will send out Beep sounds at the moment the inverter will do self diagnosis then the LED s indicators will also appear various ...

Страница 20: ...inates the red LED a Blinking fast Over input voltage OVP Check input voltage Reduce input voltage b Blinking slow Low input voltage UVP Recharge battery Check connections and cable c Blinking Intermittently Thermal shutdown OTP Improve ventilation Make sure ventilation openings in inverter are not obstructed Reduce ambient temperature d Solid ON Short circuit or Wiring error Overload OLP Check AC...

Страница 21: ...nce is required to keep your inverter operating properly You should clean the exterior of the unit periodically with a damp cloth to prevent accumulation of dust and dirt At the same time tighten the screws on the DC input terminals 19 ...

Страница 22: ...CTO DEPARTAMENTO RESPONSABLE Teléfono e MAIL Comercial y Ventas Gracia Nomparte 985319171 Ext 10 gracia amvelectronica com Ingeniería Víctor Viña 985319171 Ext 18 Producción Jenaro Blanco compras amvelectronica com Servicio de Asistencia Técnica Alejandro Arce 985319171 Ext 17 sat amvelectronica com Administración Laura Granda 985319171 Ext 12 administracion amvelectronica com ...

Страница 23: ... AMV ELECTRÓNICA SALEN DE NUESTROS TALLERES AJUSTADOS NUMERADOS Y CON DOCUMENTACIÓN TÉCNICA SIENDO LA GARANTIA TOTAL DE 2 AÑOS LA GARANTÍA CUBRE LAS SITUACIONES DE DAÑO INTRÍNSECO Y NO LAS PROVOCADAS POR CAUSAS EXTERNAS O LA MANIPULACIÓN POR PARTE DEL USUARIO LA GARANTÍA SE ENTIENDE EN NUESTROS TALLERES SIENDO POR CUENTA DEL USUARIO LOS COSTES DEL TRANSPORTE AMV ELECTRONICA ...

Отзывы: