CH-41Z/CH-80Z PIPING INSTALLATION

DOMESTIC WATER PIPING

1.  Connect the cold water supply to the pipe labeled COLD 

WATER

Do  not  apply  heat  to  this  fitting  when 

making  sweat  connections  to  heater. 

Sweat tubing to adapter before fitting adapter to cold water 

inlet of heater. It is imperative that no heat be applied to the 

cold water inlet, as it contains a nonmetallic dip tube.

2.  Connect the HOT WATER piping to the domestic hot water 

system.

3.  When all domestic water piping is complete, open the cold 

water supply and allow some water to enter the tank.  Look 

and listen for signs of leaks and repair as necessary before 

continuing.

Note:  If  installing  on  a  city  supply,  ensure  a  dedicated 

Thermal  Expansion  tank  (Therm-X-Trol

®

  or  equivalent)  is 

used.

 

Note: If a water heater is installed in a closed water supply 

system,  such  as  one  having  a  back-flow  preventer  in  the 

cold water supply line, means shall be provided to control 

thermal  expansion.  Contact  the  water  supplier  or  local 

plumbing inspector on how to control this situation.

4.  Install  a  blowdown  tube  on  the  T&P  relief  valve  outlet.  

Plumb to within 6 inches above a floor drain or as directed 

by plumbing code.

  Note: No valve is to be placed between the  T&P relief valve 

and the tank.

  Note:  Valves  for  reducing  point  of  use  temperature  by 

mixing cold and hot water are available. Consult a licensed 

plumber or the local plumbing authority.

BOILER PIPING

1.  Plumb  the  circulator  or  zone  valve  onto  the  BOILER 

SUPPLY fitting.

2.  Pipe the BOILER RETURN connection to the boiler return 

fitting.

Be  sure  the  return  line  is  NOT 

plumbed to the suction side of any 

heating  circulators.    This  may  require  moving  the 

heating circulator off the boiler tapping on packaged 

boilers.  Failure to do so will result in overheating and 

tank  damage  when  the  heating  system  is  in 

operation.

3.  Install a weighted flow check on the boiler return line.  This 

is not necessary on systems utilizing a zone valve to control 

the BoilerMate

®

 temperature.

4. After completing the boiler piping, slowly open the boiler fill 

valve and pressurize the BoilerMate

®

 loop.  Check for leaks 

and repair as necessary. Proceed to the appropriate wiring 

section in this manual.

If  installing  on  city  water  supply  a 

properly  sized  THERM-X-TROL

®

  is 

required  with  the  BoilerMate

®

  and  should  be  installed  as  set 

forth in the THERM-X-TROL

®

 product installation manual.

LEFT . . . . . . . . . . . . . . . . 1"

RIGHT. . . . . . . . . . . . . . . 1"

FRONT . . . . . . . . . . . . . 30"

HEAD ROOM . . . . . . . . 48"

REAR  . . . . . . . . . . . . . . . 1"

Recommended Clearance For Servicing

WIRING BOX

CONTROL

(AQUASTAT)

PIPING CONNECTIONS

DRAIN VALVE

AQUASTAT

BOILER RETURN

BOILER SUPPLY

TEMPERATURE
SENSOR WELL

HOT WATER

OUTLET

COLD WATER

SUPPLY

FRONT VIEW

TOP VIEW

Содержание Champion CH-41BZ

Страница 1: ...URRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE AS APPLICABLE THIS IS THE SAFETY ALERT SYMBOL IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL INJURY AS WELL AS PROPERTY DAMAGE The heat transfer medium must be water or other nontoxic fluid having a toxicity rating or class...

Страница 2: ...seepage or leakage of glycol to surfaces where humans or animals can ingest it use glycol only in double walled units so that any leaks will most likely be released to the atmosphere However a leak to a surface area may still occur so any use of glycol must be monitored closely and humans and animals should be protected from contact with the unit Do not connect the BoilerMate domestic supply with ...

Страница 3: ...iler system has an EXTROL or Radiant EXTROL expansion tank and the boiler temperatures are being changed resize the EXTROL or Radiant EXTROL expansion tank 20 15 10 5 0 0 2 4 Flow GPM Pressure Drop ft 6 8 MODEL OPTION CIRCULATOR ZONE VALVE SHUTOFF VALVE VACUUM BREAKER RELIEF VALVE THERMAL EXPASION TANK DRAIN CH 41 CH 41 CH 80 Z BZ Z 4GPM If Circulator not used 3 4 Full Port or 1 STD 4 1 Included R...

Страница 4: ...e T P relief valve and the tank Note Valves for reducing point of use temperature by mixing cold and hot water are available Consult a licensed plumber or the local plumbing authority BOILER PIPING 1 Plumb the circulator or zone valve onto the BOILER SUPPLY fitting 2 Pipe the BOILER RETURN connection to the boiler return fitting Be sure the return line is NOT plumbed to the suction side of any hea...

Страница 5: ... 5 PIPING USING DEDICATED CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR ...

Страница 6: ...ch as one having a back flow preventer in the cold water supply line means shall be provided to control thermal expansion Contact the water supplier or local plumbing inspector on how to control this situation BOILER PIPING 1 Plumb the circulator or zone valve on the BOILER SUPPLY line If using a separate circulator the pump flange can be mounted directly to the threaded pipe marked BOILER SUPPLY ...

Страница 7: ... 7 CH 41BZ PIPING USING SEPARATE CIRCULATOR PUMP RECOMMENDED PIPING USING ZONE VALVE WITH EXISTING HEATING SYSTEM CIRCULATOR ...

Страница 8: ...conduit metal clad cable or raceways Power Limited Circuit Cable need not be provided with the protection specified above if it is securely fastened to the appliance jacket and follows the contour of the appliance jacket Thermoelectric circuit wiring shall be exempt from this provision Note Strain relief shall be provided for all conductors leaving an enclosure For low voltage wiring strain relief...

Страница 9: ... Zone Relay BoilerMate Circulator BoilerMate Thermostat 1 BoilerMate THERMOSTAT 2 3 BLACK L1 HOT L2 WHITE ON BOILER CONTROL FROM BOILER CONTROL A 24 VOLT T T T T ON BOILER CONTROL END SWITCH BoilerMate THERMOSTAT FROM BOILER CONTROL BLACK L1 HOT L2 WHITE MOTOR B 24 VOLT ZONE VALVES SCHEMATIC 3 ...

Страница 10: ...dered normal and will clear as hot water is used 3 START HEATER Turn power on to the unit Dial should have the knob rotated to the 120 F mark for safety The circulator and boiler should start momentarily If not check wiring and consult the troubleshooting section in this manual 4 CHECK OPERATION The BoilerMate will begin to heat Depending upon the size of the BoilerMate output of the boiler and th...

Страница 11: ...heck valve stuck open 1 Reduce temperature setpoint 2 If Boiler Return is plumbed to the suction side of a heating circulator overheating will occur when the home s heat is on Fix plumbing 3 Fully insert temperature sensor bulb 4 Repair or replace 5 Clean repair or replace Noise from BoilerMate 1 Air in boiler loop 2 Faulty circulator pump 3 Thermal expansion 4 Normal noise during initial fill 1 P...

Страница 12: ...TS Number Description Part Number 1 Heat Exchanger w Gasket CH41Z 2703R003 2 Hot Water Outlet Tee 9403R123 3 Dip Tube CH 41Z only 2703R001 Dip Tube CH 80Z only 2702R001 4 Bottom Drain 9340R160 5 Dial Aquastat 2704 093 6 Safety Relief Valve 2700R116 7 Top Cap Assembly CH 41Z CH 80Z 2704R007 8 CH 41BZ Coil 2708R003 9 CH 80Z Coil 2702R002 5 7 6 2 1 3 Not shown ...

Страница 13: ...and leave system connections open to prevent pressure build up Electrocution Hazard The BoilerMate must be electrically grounded Electrical supply must come from the boiler side of boiler s emergency shut off switch in order to prevent unsafe operation Chlorine Aggressive Water The water quality can significantly influence the life of this Product You should test for corrosive elements acidity tot...

Страница 14: ......

Страница 15: ......

Страница 16: ...hode Island 02893 Part 9040 678 07 09 BoilerMate AMTROL AMTROL logo Therm X Trol Radiant EXTROL Champion and EXTROL are registered trademarks of AMTROL Inc and affiliates in the U S and elsewhere All rights reserved ...

Отзывы: