![Amtrol BOILERMATE CH Series Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/amtrol/boilermate-ch-series/boilermate-ch-series_installation-and-operation-instructions_2937130006.webp)
-6-
Installation - Digital Control Wiring
1.
Ensure the control installation is within the following application and
operating parameters:
• Ambient temperature from 38° to 125°F.
• Relative humidity ranging from 20% to 90% (non-condensing).
• Boiler load rating up to 15A resistive, 1/4hp inductive @ 120VAC.
• Circulator load rating up to 15A, 1/4hp inductive @ 120VAC.
• Space heating load rating up to 8A @ 120VAC.
NOTE:
Line-voltage and safety-circuit wiring that is external to the
water heater jacket when all panels are in place, and which is part of
the appliance, shall be protected by metal conduit, metal-clad cable or
raceways. Thermoelectric wiring shall be exempt from this provision.
NOTE:
Strain relief shall be provided for all conductors leaving an
enclosure. For low-voltage wiring, strain relief at the point of exit from an
enclosure is not necessary if, by wire location or support, protection is
provided against accidental strain.
BOILERMATE
CIRCULATOR
HEATING
CIRCULATOR
ORANGE
ORANGE
WHITE
BLACK
BLUE
BLUE
VIOLET
VIOLET
POWER BURNER
PUMP
PRIORITY
ZR Input Terminal
L1
ZR
C1
C2
L2
BOILERMATE
CIRCULATOR
HEATING
CIRCULATOR
ORANGE
ORANGE
WHITE
BLACK
BLUE
BLUE
VIOLET
VIOLET
POWER BURNER
PUMP
PRIORITY
24 Volt
L1
B
Z
W
C1
C2
L2
BOILERMATE
CIRCULATOR
DHW ZONE
ORANGE
ORANGE
WHITE
BLACK
BLUE
BLUE
VIOLET
VIOLET
POWER BURNER
PUMP
PRIORITY
Multi-Zone Control: Using Post Purge
L1
L2
TO BOILER
X
X
BOILERMATE
CIRCULATOR
HEATING
CIRCULATOR
ORANGE
ORANGE
WHITE
BLACK
BLUE
BLUE
VIOLET
VIOLET
POWER BURNER
PUMP
PRIORITY
High Limit (B Terminal)
L1
B
C1
C2
L2
ORANGE
ORANGE
WHITE
BLACK
BLUE
BLUE
VIOLET
VIOLET
POWER BURNER
PUMP
PRIORITY
BOILERMATE
CIRCULATOR
HEATING
CIRCULATOR
L1
B
B2
Z
W
C1
C2
L2
Millivolt
BOILERMATE
CIRCULATOR
OR ZONE VALVE
DHW ZONE
24 OR 120VAC
ORANGE
ORANGE
WHITE
BLACK
BLUE
BLUE
VIOLET
VIOLET
POWER BURNER
PUMP
PRIORITY
Multi-Zone Control: No Post Purge
L1
L2
TO BOILER
X
X
BOILERMATE
®
CIRCULATOR
Z
I
ORANGE
ORANGE
WHITE
BLACK
BLUE
BLUE
VIOLET
VIOLET
POWER BURNER
PUMP
PRIORITY
Outdoor Reset/Automatic Temperature Control
L1
ZC
ZR
L2
ZONE/INDRIECT SWITCH
(IF EQUIPPED)
SELECT “INDIRECT”
BOILERMATE
CIRCULATOR
HEATING
CIRCULATOR
ORANGE
ORANGE
WHITE
BLACK
BLUE
BLUE
VIOLET
VIOLET
POWER BURNER
PUMP
PRIORITY
Triple-Aquastat
L1
B
R
C1
C2
L2
BOILERMATE
CIRCULATOR
HEATING
CIRCULATOR
ORANGE
ORANGE
WHITE
BLACK
BLUE
BLUE
VIOLET
VIOLET
POWER BURNER
PUMP
PRIORITY
L1
B
B2
C1
C2
L2
Self-Generating
ZONE VALVE
END
SWITCH
MOTOR
24VAC
ORANGE
ORANGE
WHITE
BLACK
BLUE
BLUE
VIOLET
VIOLET
POWER BURNER
PUMP
PRIORITY
4-Wire Zone Valve
TRANSFORMER
L1
L2
Oil Burner Controls
Gas Valve Controls
Other Applications
Note: if your application is not shown, contact AMTROL Technical Support at 401.535.1216.