background image

 

Innovative Circuit Technology Ltd. 

 

Status Indicators and Alarms 

The 2 LEDs on the front panel and the Form-C alarm contacts on the back 
indicate the status of the power supply: 
 

Alarm or 

Notification 

Trigger Condition 

LOAD 

Output 

BATT 

LVD 

Red 

FAULT 

LED 

Green 

POWER 

LED 

Input AC OK, 
battery charging 

Normal operation, 
battery charging

 

Enabled  Enabled 

-

 

ON

 

Input AC OK, 
battery charged 

Normal operation, 
battery charged  

Enabled  Enabled 

ON 

AC Under-
voltage Warning

 

Triggers when Input 
Voltage drops below 
approx. 90Vac 

Enabled  Enabled 

ON

 

ON

 

AC Fail 

AC fails or front switch 
is off (Battery above 
LVD level) 

Battery 
power 
only 

Enabled 

ON 

Battery Low 

(when AC Off)

 

Triggers when battery 
voltage falls below the 
LVD threshold 

OFF  

OFF 

ON 

System Fault 

Indicates internal 
circuit fault - Clears 
when all fault 
conditions are cleared. 

Battery 
power 
only 

Enabled 

ON 

Dead or 
Disconnected 
Battery 

(AC 

present)

 

Battery voltage is less 
than 5/10/20V (on 
12/24/48V models) 
No charging  

Enabled  OFF 

ON 

Battery Over 
Voltage Fault 

(AC present)

 

Triggers when the 
battery voltage 
exceeds the internal 
OVP threshold for 3s 

Enabled  OFF 

ON 

ON 

DC Overvoltage 
Shutdown 

Triggers for output 
voltage above 

16.5/33/66VDC 

for 

1s.

 

Clears when Input 
power cycled off/on 

Battery 
power 
only 

Enabled 

ON 

Over-
temperature 
Shutdown 

Triggers when internal 
temperature is too 
high.  Clears when 
back to normal range. 

Battery 
Power 
only 

Enabled 

ON 

The form-C alarm contact will be triggered for any condition that lights the red 
FAULT LED, or shuts down the output of the unit. 

All manuals and user guides at all-guides.com

Содержание ICT1190-12S

Страница 1: ...odels ICT690 12S ICT690 12SB ICT690 24S ICT690 24SB ICT690 48S ICT690 48SB ICT1190 12S ICT1190 12SB ICT1190 24S ICT1190 24SB ICT1190 48S ICT1190 48SB DC Power Solutions not just components All manuals...

Страница 2: ...n and service is done with the battery de energised Use wire and connectors rated for the maximum load current and size of battery fuse or circuit breaker Ensure battery polarity is correct before con...

Страница 3: ...nology Ltd 3 Table of Contents INTRODUCTION 4 CHECK and CONFIGURE UNIT 4 INSTALLATION 6 OPERATION 7 Status Indicators and Alarms 9 PRODUCT SPECIFICATIONS 10 LIMITED WARRANTY 12 All manuals and user gu...

Страница 4: ...ol input for external control of the output Floating Form C alarm contact output supports remote monitoring of unit operation Model 1 Output Voltage V Max Output Current A Continuous Current A ICT690...

Страница 5: ...red Do not ground both the load and battery as this may bypass the internal LVD circuitry AC input wiring to the Pro Series unit must be protected using an outlet with a branch rated circuit breaker o...

Страница 6: ...Setting 12V 24V 48V BAT SW1 Setting BAT SW2 Setting Disconnect V Default 11 5 23 46 x 1 Disconnect V low setting 10 5 21 42 x 0 Reconnect V Default 12 5 25 50 1 x Reconnect V low setting 12 24 48 0 x...

Страница 7: ...ways connected to the battery positive as shown NOTE Do not ground the battery POS terminal as this may bypass the internal LVD relay Connect the remote on off control or unit form C alarm contact mon...

Страница 8: ...setting of SW 3 and 4 see table on page 5 while the output voltage will be determined by the battery state of charge and will rise to the output float voltage over time The battery will be maintained...

Страница 9: ...falls below the LVD threshold OFF OFF ON System Fault Indicates internal circuit fault Clears when all fault conditions are cleared Battery power only Enabled ON Dead or Disconnected Battery AC prese...

Страница 10: ...3 1200W 690W 1200W 690W 1200W 690W Output Noise max mVrms 30 30 30 30 40 40 Input Current max at 120Vac 12A 7A 12A 7A 12A 7A LVD Threshold V Default 11 5V 11 5V 23 0V 23 0V 46 0V 46 0V LVD Reconnect...

Страница 11: ...equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there i...

Страница 12: ...uct manuals and promotional materials accurately describe ICT product specifications and capabilities at the time of publication However because of ongoing improvements and updating of ICT products IC...

Отзывы: