background image

Innovative Circuit Technology Ltd.

 

WARNING 

Risk of serious personal injury or damage to equipment and property! Always 
observe the following: 

 

Install and operate unit in a Restricted Access location, such as an enclosed 
equipment rack 

 

Operate the supply from a grounded 3-pin 120Vac or 230Vac outlet (50 or 
60Hz) with a branch circuit breaker rated 20A or less 

 
Always observe the following for applications requiring a back up battery: 

 

Use only a Lead-Acid battery with rating and capacity appropriate for the 
model of supply in use 

 

Use an appropriate dc over-current protection device in line with the back-
up battery connection 

 

Use a disconnect switch or circuit breaker in series with the battery 
connection, to ensure installation and service is done with the battery de-
energised 

 

Use wire and connectors rated for the maximum load current and size of 
battery fuse or circuit breaker 

 

Ensure battery polarity is correct before connecting 

 

Do not attempt to charge a frozen battery 

 

Handle batteries with care, never short circuit battery terminals 

 
 

CAUTION 

Risk of personal injury or damage to equipment! Always observe the following: 

 

Install in a protected environment, keep sources of moisture away from unit 

 

Ensure the total power consumption of the load does not exceed the 
continuous rated capacity of the power supply output 

 

Do not block air inlet or outlet openings in the unit 

 

Do not place the power supply directly above or below an exposed battery, 
due to possible presence of corrosive and/or flammable gasses 

 

Do not add a ground connection to both battery and load, as this will bypass 
the internal LVD relay 

 

 

All manuals and user guides at all-guides.com

Содержание ICT1190-12S

Страница 1: ...odels ICT690 12S ICT690 12SB ICT690 24S ICT690 24SB ICT690 48S ICT690 48SB ICT1190 12S ICT1190 12SB ICT1190 24S ICT1190 24SB ICT1190 48S ICT1190 48SB DC Power Solutions not just components All manuals...

Страница 2: ...n and service is done with the battery de energised Use wire and connectors rated for the maximum load current and size of battery fuse or circuit breaker Ensure battery polarity is correct before con...

Страница 3: ...nology Ltd 3 Table of Contents INTRODUCTION 4 CHECK and CONFIGURE UNIT 4 INSTALLATION 6 OPERATION 7 Status Indicators and Alarms 9 PRODUCT SPECIFICATIONS 10 LIMITED WARRANTY 12 All manuals and user gu...

Страница 4: ...ol input for external control of the output Floating Form C alarm contact output supports remote monitoring of unit operation Model 1 Output Voltage V Max Output Current A Continuous Current A ICT690...

Страница 5: ...red Do not ground both the load and battery as this may bypass the internal LVD circuitry AC input wiring to the Pro Series unit must be protected using an outlet with a branch rated circuit breaker o...

Страница 6: ...Setting 12V 24V 48V BAT SW1 Setting BAT SW2 Setting Disconnect V Default 11 5 23 46 x 1 Disconnect V low setting 10 5 21 42 x 0 Reconnect V Default 12 5 25 50 1 x Reconnect V low setting 12 24 48 0 x...

Страница 7: ...ways connected to the battery positive as shown NOTE Do not ground the battery POS terminal as this may bypass the internal LVD relay Connect the remote on off control or unit form C alarm contact mon...

Страница 8: ...setting of SW 3 and 4 see table on page 5 while the output voltage will be determined by the battery state of charge and will rise to the output float voltage over time The battery will be maintained...

Страница 9: ...falls below the LVD threshold OFF OFF ON System Fault Indicates internal circuit fault Clears when all fault conditions are cleared Battery power only Enabled ON Dead or Disconnected Battery AC prese...

Страница 10: ...3 1200W 690W 1200W 690W 1200W 690W Output Noise max mVrms 30 30 30 30 40 40 Input Current max at 120Vac 12A 7A 12A 7A 12A 7A LVD Threshold V Default 11 5V 11 5V 23 0V 23 0V 46 0V 46 0V LVD Reconnect...

Страница 11: ...equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there i...

Страница 12: ...uct manuals and promotional materials accurately describe ICT product specifications and capabilities at the time of publication However because of ongoing improvements and updating of ICT products IC...