Innovative Circuit Technology Ltd.
WARNING
Risk of serious personal injury or damage to equipment and property! Always
observe the following:
Install and operate unit in a Restricted Access location, such as an enclosed
equipment rack
Operate the supply from a grounded 3-pin 120Vac or 230Vac outlet (50 or
60Hz) with a branch circuit breaker rated 20A or less
Always observe the following for applications requiring a back up battery:
Use only a Lead-Acid battery with rating and capacity appropriate for the
model of supply in use
Use an appropriate dc over-current protection device in line with the back-
up battery connection
Use a disconnect switch or circuit breaker in series with the battery
connection, to ensure installation and service is done with the battery de-
energised
Use wire and connectors rated for the maximum load current and size of
battery fuse or circuit breaker
Ensure battery polarity is correct before connecting
Do not attempt to charge a frozen battery
Handle batteries with care, never short circuit battery terminals
CAUTION
Risk of personal injury or damage to equipment! Always observe the following:
Install in a protected environment, keep sources of moisture away from unit
Ensure the total power consumption of the load does not exceed the
continuous rated capacity of the power supply output
Do not block air inlet or outlet openings in the unit
Do not place the power supply directly above or below an exposed battery,
due to possible presence of corrosive and/or flammable gasses
Do not add a ground connection to both battery and load, as this will bypass
the internal LVD relay