8
Display parameters of the additional display:
_________________________________________________________
Display
Display
Description
selection
T4 (EIN)
_________________________________________________________
1
h
operating time
2
Wh
active energy,
received
3
varh
reactive energy,
inductive
4
display OFF
4.
Setup
4.1
General notes
When using the multifunction meter for the first time in a specific environment the MFA 2001 needs
to be adapted to the attached periphery using the setup mode.
To activate setup mode press both the T1 and T2 key simultaneously for at least 3 seconds.
The MFA 2001 always starts in setup mode with the setup option
ƒ
Setup of the voltage transformer translation ratio („V, V, ADJUST…)
The T2 ( ‚ ) key can be used to proceed through the selection in the following order:
ƒ
Setup of the current transformer translation ratio („A, A, ADJUST…)
ƒ
Selection of the integration time to calculate average values („sec…)
ƒ
Selection of all criteria for limit value 1 („LIMIT 1 ADJUST…)
ƒ
Selection of all criteria for limit value 2 („LIMIT 2 ADJUST…)
ƒ
Delete and reset functions („LOE ADJUST…)
ƒ
Password („PAS ADJUST…)
ƒ
RS 485 alt. Profibus DP („OP1 ADJUST…),
option 1
ƒ
Analogue output („OP2 ADJUST…),
option 2
The displayed setup option is activated by pressing the T3 (OPT).
Press the T3 (OPT) key again to exit the setup menu.
It is possible to exit setup mode at any point by pressing the T4 key.
Any changes made up to that point are saved.