14
5. Setting the
response value
. A preset value relevant to the selection of parameters and phases
is displayed with the first digit flashing.
With the T1 ( ‡ ) key the value can be increased starting at …0ˆ through to …9ˆ. To access a lower
value press the T1 ( ‡ ) key past …9ˆ to start again with …0ˆ.
Press the T2 ( ‚ ) key to access the next digit. The digit starts flashing. To change the value press
T1 ( ‡ ) key.
After setting the last digit the decimal point starts flashing and can now be moved by pressing the
T1 ( ‡ ) key. Also the measuring range …kˆ can be selected or changed to …Mˆ where required.
6. Press the T2 ( ‚ ) key again and the …minˆ display starts flashing.
„min…: Alarm is triggered when falling below the set value
„max…: Alarm is triggered when exceeding the set value
Press the T1 ( ‡ )
key to select „min… or „max….
By pressing the T2 ( ‚ ) key the complete process of setting response value can be repeated.
The process is completed by pressing T3 (OPT) key. The setup menu is displayed.
Setup as impulse output:
The impulse valancy specified in Wh/impulse or kWh/impulse.
Impulse valancy = energy per impulse
Due to technical reasons the denomination “Wh” appears
at
the bottom of the display. If the range “kWh” is selected the
“k” apears apart from the “Wh” right hand from the impulse valency to be set.
1. Select and activate the impulse counter function (see 2. above) by pressing T3 (OPT).
2. Setting the
i
mpulse rate
. A
preset value relevant to the impulse rate is displayed with the first
digit flashing.
With the T1 ( ‡ )
key the value can be increased starting at …0ˆ through to …9ˆ. To access a lower
value press the T1 ( ‡ )
key past …9ˆ to start again with …0ˆ.
Press the T2 ( ‚ ) key to access the next digit. The digit starts flashing. To change the value press
T1 ( ‡ )
key.
After setting the last digit the decimal point starts flashing and can now be moved by pressing the
T1 ( ‡ )
key. Also the measuring range …kˆ can be selected where required.
The process is completed by pressing T3 (OPT) key. The setup menu is displayed.
Deactivating the limit value output
The limit output can also be deactivated.
1. Select deactivation and activation of the limit output (see 2. above) by pressing T3 (OPT).
2. LIMIT 1
AUS
ADJUST
is displayed with …AUSˆ flashing.
3. By pressing T3 (OPT) key the limit output is deactivated and the setup menu is displayed.
The parameters for limit value 2 (LIMIT 2)
are set the same way.