Amron 9000-ECS Скачать руководство пользователя страница 11

 

MODEL 9000-ECS USER MANUAL 

 

 

 

9000-ECS-UM 

REV 4.0 

The resulting temperature drop causes the Freon gas to change from a gaseous state to a 
liquid form.  

The Freon liquid/gas from the output of the condenser is collected in the accumulator. The 
accumulator buffers the pressure pulses from the compressor and provides a collection point 
(reservoir) to draw off liquid Freon. The Freon then goes through a filter/drier to remove any 
foreign particles, and ensure no particles reach the expansion valve. A sight gauge is 
provided on the output of the filter/drier as a visual indication of the status of the system.  

If you watch the sight glass during normal operation of the system you will see the Freon 
flowing through the system. At normal room temperatures 70

o

 F (21

o

 C) you will see a small 

amount of bubbles in the liquid. This is normal, if the operating temperature goes up the 
amount of bubbles will increase and if the temperature goes down the amount of bubbles will 
decrease to the point where there will be none. 

The expansion valve controls the flow of liquid Freon into the evaporator, where the Freon 
under a lower pressure expands and changes to a gas. This change from liquid to gas 
absorbs heat providing the cooling desired. The expansion valve is controlled by a temp bulb 
sensing the temperature on the output of the evaporator. If the temperature is high (or equal 
to the temperature of the expansion valve) the valve opens allowing more Freon into the 
evaporator. This continues until the temperature at the output of the evaporator drops, and 
the valve throttles the flow of Freon.  

The Freon circuit achieves a balanced condition when the spring force of the expansion 
valve, refrigerant pressure/temperature, and evaporator pressure/temperature results in the 
proper flow of Freon achieving the desired cooling. The design of the system determines 
proper operation as opposed to adjustments. Expansion valves are adjustable; however, this 
is set by the manufacture of the valves and is not a field procedure. 

The evaporator is a two-circuit system and uses a Freon distributor to feed the two circuits of 
the evaporator coil. The expansion valve, distributor, evaporator coil, and compressor 
system are sized to achieve the desired end result. It is not recommended that part 
substitutions be made. The Freon vapor returns to the compressor (suction side) completing 
the refrigerant cycle. 

 

FLUID SYSTEM 

4.3

The fluid system might be considered the heart of the system. This is where heat is added 
to, or subtracted from the system. The fluid, heated or cooled is then pumped to the 
chamber inside conditioning unit. The chamber inside conditioning system consists of a set 
of coils, where a fan blows air across the coils producing heat or cooling.  

The fluid system consists of a reservoir, pump, temperature meters, and associated 
plumbing. The reservoir contains a fluid that is heated or cooled, (depending on the mode 
selected), which is then pumped to the chamber heat exchanger where heat is extracted or 
added to achieve the desired end result. 

Because of the low temperature range of the unit (20o F), it is necessary to extend the 
operating range of the fluid by adding antifreeze to the water. Use either ethylene glycol or 
propylene glycol, in the ratio of 50% glycol to 50% water. The reservoir holds approximately 
7 gallons of fluid; therefore it will be necessary to add approximately 3.5 gallons of glycol. 

Содержание 9000-ECS

Страница 1: ...760 599 3857 Email sales amronintl com Web www amronintl com This manual and the information contained herein are provided for use as an operation and maintenance guide No license or rights to manufac...

Страница 2: ......

Страница 3: ...N 6 GENERAL 6 4 1 REFRIGERATION 6 4 2 FLUID SYSTEM 7 4 3 ELECTRICAL SYSTEM 8 4 4 5 INSTALLATION 9 LOCATION 9 5 1 ELECTRICAL 9 5 2 6 OPERATION 10 7 MAINTENANCE AND TROUBLESHOOTING 11 GENERAL 11 7 1 TRO...

Страница 4: ...i 9 PARTS LIST GENERAL 25 9000 ECS ENVIRONMENTAL CONDITIONING SYSTEMS 26 9 1 9000 400 RESERVOIR SUB ASSEMBLY 27 9 2 9000 500 ELECTRICAL SUB ASSEMBLY 28 9 3 AC 5C MD 230V CIRCULATING PUMP 1 8 HP 230V 2...

Страница 5: ...ts ranging in size from 54 inch through 72 inch diameters There are certain conditions where the heat load may exceed the capacity of the unit These conditions may occur when the chamber is being pres...

Страница 6: ...120 o C Accuracy 1 of Full Scale Refrigerant Compressor Sealed Unit Refrigerant Freon R 404A Protection Internal Thermal Overload Locked Rotor Current 45 Amps Nominal Current Draw 6 4 Amps Restart Int...

Страница 7: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 3 MODEL 9000 ECS 1 3...

Страница 8: ...4 2 OPTIONS Model 9000 RCS Remote control switch allows remote control of the Model 9000 ECS The 25 foot remote control cable connects to the remote control connector on the Model 9000 ECS and permit...

Страница 9: ...C RETURN THERMOMETER 3 4 Three inch dial dual scale thermometer reads fluid temperature returning to the system Temperature range 0 o to 250 o F 20 o to 120 o C FLUID LEVEL INDICATOR 3 5 Slight glass...

Страница 10: ...ts of a fluid system reservoir pump to store and circulate the water a refrigeration unit to cool the water a heater to heat the water and controls to select the mode of operation Internal temperature...

Страница 11: ...circuit achieves a balanced condition when the spring force of the expansion valve refrigerant pressure temperature and evaporator pressure temperature results in the proper flow of Freon achieving t...

Страница 12: ...ase 50 60 Hz The unit requires a 15 amp fused circuit preferably from a separate disconnect box located close to the system The heater and pump have separate internal fuses The heater is fused at 15 a...

Страница 13: ...t be connected via a quick disconnect box with 15 amp fuses Power requirements are 220 VAC 50 60 Hz single phase Voltage limits are 187 to 250 VAC this allows the unit to operate on either a 220 or 20...

Страница 14: ...there will be a delay of approximately 45 seconds before the compressor starts This allows the pressures within the compressor to bleed off permitting easier starting and eliminates nuisance blowing...

Страница 15: ...eservoir An easy way to adjust the controller is to note the present setting of the controller and the point at which the heater did shut off and adjust accordingly Example The unit shut off at 100 o...

Страница 16: ...Cause Unit does not cool Check Freon charge Unit does not run Check power to unit Unit does not run power OK Check fuses to pump Unit does not run power OK fuses OK Check for 24 VAC Unit will not hea...

Страница 17: ...following drawings illustrate the electrical and mechanical details of the External Conditioning System unit The drawings reference identifier numbers correspond to the parts list identifier numbers...

Страница 18: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 14 MODEL 9000 ECS SPECIFICATIONS 8 1...

Страница 19: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 15 CHAMBER CONDITIONING CONNECTION DIAGRAM 8 2...

Страница 20: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 16 9000 ECS BLOCK DIAGRAM 8 3...

Страница 21: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 17 ELECTRICAL SCHEMATIC 8 4...

Страница 22: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 18 REMOTE CONTROL WIRING DIAGRAM 8 5...

Страница 23: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 19 PARTS LOCATOR EXTERIOR 8 6...

Страница 24: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 20 PARTS LOCATOR FRONT VIEW 8 7...

Страница 25: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 21 PARTS LOCATOR REAR VIEW 8 8...

Страница 26: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 22 PARTS LOCATOR TOP VIEW 8 9...

Страница 27: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 23 PARTS LOCATOR ELECTRICAL CONTROL BOX 8 10...

Страница 28: ...MODEL 9000 ECS USER MANUAL 9000 ECS UM REV 4 0 24 PARTS LOCATOR CIRCULATING PUMP PN AC 5C MD 230V 8 11...

Страница 29: ...er Replacement Parts Contact Amron International Inc 1380 Aspen Way Vista California 92081 U S A Telephone 760 208 6500 Fax 760 599 3857 Email sales amronintl com Web www amronintl com When ordering r...

Страница 30: ...D 16 0512 100 Tubing Braid reinforced 3 4 I D NS 125HBL 10 8 Hose Barb to male pipe brass NS 125HBL 12 12 Hose Barb to male pipe brass 19 129HB 12 12 Hose Barb 90 elbow to male pipe 20 PTR B 1 X 3 4 P...

Страница 31: ...Union 5 8 Brass 42 ECEB4X1 5 Elect Conduit Ext Box 4 X 1 5 43 3219 Grommet 230 546 dia Hole NS ECNP1 2X4 Elect Conduit Nipple 1 2 X 4 NS ECEL1 2 Elect Conduit Ell 1 2M 1 2F 46 A19ABC 4 Thermostat 50 T...

Страница 32: ...ontactor DPDT 24 VAC 62 S84Z 401 Transformer 24 VAC 40VA NS 9000 021 Cover Junction Box 64 9000 019 Bracket Electrical Connection 55 9000 018 Plate Junction Box Mounting 65 SO 14 3 Cableso Type14 AWG3...

Страница 33: ...Cover 4 O ring Buna N 4A O Ring Vito 5 Ceramic Thrust Washer 7 Spindle 8 Impeller magnet Assembly 8A Impeller Magnet Assembly W Stainless Cover 8B Impeller Magnet Assembly W Bronze Bushing 8C Impeller...

Страница 34: ...ccident repair or alterations SERVICE POLICY For technical assistance or to request a repair please complete one of the following Amron Communicator Repair https www amronintl com communicator repair...

Отзывы: