Amphenol PowerLok PL182X-301-50 Скачать руководство пользователя страница 3

(3), 

以布线状态拉动线束靠近合金外壳,

转动R4 holder, 使其止转切面与合金外壳的2/3pos中心连线相

垂直;        

并保持R4 holder与线缆相对位置;

drag the cable end close to alloy shell in service 

state,

rotate R4 holder, have its anti-rotation chamfer surface vertical to link line of the 2/3pos 

center in alloy shell;        

hold relative position of R4 holder & cable;

(4), 

拉直线缆

记录此时R4 holder 止转切面与步骤

9

已组装完成端插头的相对角度, 并记录;        

stretch 

the cable, record angle between R4 holder anti-rotation chamfer surface and plug end assembled 

done in step

9

;

(5), 

拔下合金外壳;        

remove the alloy shell from receptacle; 

3 of 3

Rev. 2

®

11

,

组装线束

另一端

assemble plug on 

the other end 

of cable.

10, 

将步骤

9

组装好的插头插接到 对应的PDU/负

载插座上.    

plug the connector end done in 

step

9

to corresponding PDU or load 

receptacle panel.

(1), 再

取一套零件, 按步骤1~4操作, 套上端子,

暂不压接端子

;    

take another set plug components, 

assemble as step 1~4, then load a R4 holder to the end, 

pending crimping

;

(6), 

保持步骤(

3

)R4 holder与线缆的相对位置, 按照步骤5~9,压接线束, 完成线束另一端组装;

hold 

relative position of R4 holder & cable as in step(

3

), 

follow step5~9, crimp cable, complete 

connector assemble of this end;
(7), 

将步骤(4)记录的角度/位置写入作业指引, 后续即按该旋转角度操作, 进行批量压接/组装. 

record 

the R4 rotation angle/position in step(4), form an operation instruction for mass assembly.

PDU or 

load负载

front view

正视图

Left view

左视图

(2), 

取1pcs合金外壳, 将其开口对准并插入(PDU或负载的)插座, 放置待用;    

take an alloy shell, align its 

open with receptacle(on PDU or load panel), plug in, put it aside;

anti-rotation chamfers face ceiling & ground.

alloy shell

合金外壳

Receptacle

插座

注意

如线束待组装的另一端

采用止转

R4

端子

请忽略以下步骤

否则

请严格按以下步骤实施线束另一端的组

装 !

If the other end to be assembled doesn’t adopt R4 holder with anti-rotation chamfer, then 

ignore following steps, or please strictly follow following steps to assemble the other end!

R4 holder

receptacle fixed on 

load or 

PDU

插座

Plug in to 

engage the 

two 

插入

HVIL align 

压互锁位对齐

anti-rotation 

chamfer

止转切面

vertical yellow line is 

the pos link line

黄竖

线为两

/

三芯中心连线

.

2/3pos PowerLok 直头组装式插头安装规范(屏蔽款)

2/3pos PowerLok 180D Plug Assembly Specification(shielded

)

SS ring1

Rubber ring

end cap

R4 holder with anti-rotation 

chamfer  带止转切面的R4端子.

SS ring1