![Amphenol PowerLok PL182X-301-50 Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/amphenol/powerlok-pl182x-301-50/powerlok-pl182x-301-50_manual_2934615002.webp)
2 of 3
™
Rev.2
®
6
,
取1pcs的
⑤
R4 holder 自左端穿上线缆,并压接在其上(规格参照下表);
take a
⑤
R4 holder, load it to the cable end
on the left, then crimp(refer to crimping spec below);
⑤
R4
holder
端子
7,
组装
⑥
绝缘筒 到R4 holder脖颈处的沟槽;
snap on the
⑥
insulation sleeve to the R4 holder neck groove
;
8,
插入
⑤
R4 holder到
⑦
绝缘罩上,
转动
使其触底; 以相同方法装配另一/二条线束的一端;
plug the
⑤
R4 holder to the
⑦
insulation cap,
rotate
to have it contact the bottom; assemble one end of other pos
cables in the same way as step 1~8.
⑦
insulation
cap
绝缘罩
make sure R4 end visible &
reach the insulation cap edge
open.
Plug the R4 holder to the insulation cap,
rotate
to have it contact the bottom.
⑤
R4 holder
⑥
Insulation
sleeve
绝缘筒
连接器
Connector
线缆尺寸
Cable size
线缆外径
Accepted
cable OD (mm)
压接高度
Crimping
height (mm)
参考抗拉拔力
Retention Force
300
系列
Series
35mm²
14.5
±
0.50
9.6+0/-0.2
2200N
50mm²
17.0
±
0.50
12.0+0/-0.2
2700N
70mm²
19.5
±
0.50
13.2+0/-0.2
3300N
线缆压接规格&拉拔力要求
Crimping spec & retention force requirement
Screw the end cap tight, torque
10~12N·M.
拧紧力矩
10
~
12
牛米
.
9
,
插入
⑥
绝缘罩到
⑧
合金外壳,
转动
, 使其触底; 以10~12N∙M拧紧①尾盖,完成此端线束的组装; p
lug the
⑥
insulation cap into
⑧
alloy shell,
rotate
to have it reach the bottom, screw
①
end cap tight with torque
10~12N·M, one end assembly done;
⑥
Insulation
cap
绝缘罩
⑧
alloy shell
合金外壳
2/3pos PowerLok 直头组装式插头安装规范(屏蔽款)
2/3pos PowerLok 180D Plug Assembly Specification(shielded
)
crimp cable here
此处压接线束