Amphenol PowerLok PL182X-301-50 Скачать руководство пользователя страница 2

2 of 3

Rev.2

®

6

取1pcs的

R4 holder 自左端穿上线缆,并压接在其上(规格参照下表);

take a 

R4 holder, load it to the cable end 

on the left, then crimp(refer to crimping spec below);

R4

 

holder

 

端子

7, 

组装

绝缘筒 到R4 holder脖颈处的沟槽;    

snap on the 

insulation sleeve to the R4 holder neck groove

;

8, 

插入

R4 holder到

绝缘罩上, 

转动

使其触底;        以相同方法装配另一/二条线束的一端;

plug the

R4 holder to the 

insulation cap, 

rotate

to have it contact the bottom;        assemble one end of other pos

cables in the same way as step 1~8.

insulation 

cap 

绝缘罩

make sure R4 end visible & 

reach the insulation cap edge 

open.

Plug the R4 holder to the insulation cap, 

rotate

to have it contact the bottom.

R4 holder

Insulation 

sleeve

绝缘筒

连接器

Connector

线缆尺寸

Cable size 

线缆外径

Accepted 

cable OD (mm)

压接高度

Crimping 

height (mm)

参考抗拉拔力

Retention Force

300

系列

Series

35mm²

14.5

±

0.50

9.6+0/-0.2

2200N

50mm²

17.0

±

0.50

12.0+0/-0.2

2700N

70mm²

19.5

±

0.50

13.2+0/-0.2

3300N

线缆压接规格&拉拔力要求

Crimping spec & retention force requirement 

Screw the end cap tight, torque 

10~12N·M. 

拧紧力矩

10

12

牛米

.

9

,

插入

绝缘罩到

合金外壳, 

转动

, 使其触底; 以10~12N∙M拧紧①尾盖,完成此端线束的组装;   p

lug the 

insulation cap into 

alloy shell, 

rotate

to have it reach the bottom, screw 

end cap tight with torque 

10~12N·M, one end assembly done;

Insulation

cap 

绝缘罩

alloy shell 

合金外壳

2/3pos PowerLok 直头组装式插头安装规范(屏蔽款)

2/3pos PowerLok 180D Plug Assembly Specification(shielded

)

crimp cable here 

此处压接线束