19
240GT54/nrg240GT54
Amphenol Network Solutions
All rights reserved. 6.5.2020 150567
509.926.6000
— amphenol-ns.com.com
NOTE:
For nrgSMART panel only. When removing or installing new GMT fuses, TPA fuses, or circuit
breakers, ensure the changes are updated in the nrgSMART configuration wizard.
21.
With all the GMT positions uninstalled, TPA fuse holders
empty,
or breakers off
enable the breaker at the primary
distribution unit or battery, 125% of panel rating (for 240A rated
feeds) to turn on Feed A to Side A of the panel. Check voltage
and polarity at input connectors of the panel.
Verify the following:
•
A PWR LED on the front of panel turns green
•
A ALM LED on the front of panel turns red
•
B PWR LED remains off
•
B ALM LED remains off
22. With A PWR LED green (normal operation) and A ALM LED
red
(alarm state)
— but with B PWR LED and B ALM LED off
— test ALM relay and contact alarm terminals:
•
Expect an open circuit (∞Ω) between terminals C and NC
•
Expect continuity (0Ω) between terminals C and NO
23. With no output wires connected or with the output loads (devices fed by this panel) disabled, install GMT
fuses and TPA fuses into the fuse holders or turn on breakers, see section 2.2.9 and 2.2.10.
Verify the following:
•
A PWR LED on the front of panel turns green
•
A ALM LED turns off
•
B PWR LED remains off
•
B ALM LED remains off
24. If A ALM LED is red, verify that all of the DIP switches for all empty TPA fuse or circuit breaker positions
are up (OFF).
25. With A PWR LED green (normal operation) and A ALM LED off (normal state)
—but with B PWR LED and
B ALM LED off
— test A ALM relay and contact terminals:
•
Expect continuity (0
Ω) between terminals C and NC
•
Expect an open circuit (
∞Ω) between terminals C and NO
26. Repeat steps 21-25 to power up side B. A PWR and B PWR LEDs must both be green.
27. Reinstall the cover to the front of the panel using the thumb screws or a Phillips screwdriver.
A PWR
LED
B ALM
LED
A ALM
LED
B PWR
LED
Fig. 2-10: 240GT54 LED Status
nrg
LED
Содержание 240GT54