background image

Ampetronic MLD5 Installation Handbook

Page 10

wires should be kept well apart from each other. To avoid interference maintain a separation 

of at least 300mm.

4.  Instability can cause the amplifier to run hot and may result in the TEMP LED illuminating.

Interference

1.  Background magnetic field signals or interference may be present in any location and may not 

be anything to do with the loop system. Monitor this with a loop receiver (such as an ILR3). If 

the interference is still present with the loop system switched off, then you need to locate and 

eliminate the source of the interference before switching the loop system back on

2.  Magnetic fields can induce currents into any low impedance electrical path or loop. Audio or 

video systems with multiple earths may experience pick up of the loop signal. Check entire 

sound system for evidence of loop signal, and trace source of pick up.

3.  Under certain circumstances, the loop signal may appear as jagged lines or hum bars on a 

CCTV picture. This could be due to running CCTV (low impedance unbalanced 2-wire circuit) 

cables in close proximity to the loop cable. Separate the loop cables to reduce the effect.

4.  Remote (and apparently unconnected) PA systems can sometimes pick up loop signals. This 

is usually because the loop cable becomes damaged (see point 1 of Instability) or induces 

signals into the remote system through long unbalanced cables. Always run long audio signal 

cables as 3-wire balanced circuits and keep away from loop cables.

5.  See also point 1 of Instability

Failed AC power fuse in rear of unit

Unplug the loop and AC power supply from amplifier, and replace the failed fuse with the spare fuse 

in AC power input fuse tray. 
Reconnect the AC power supply and switch on. If the fuse fails again, return the unit to Ampetronic 

for evaluation - it may well be covered under warranty, which will be invalidated by removing the 

cover. If the fuse does not fail a 'loop error' may be indicated, but shows that the unit is working 

correctly. Re-connect the loop and switch the power off then on again to reset loop error.
If the fuse fails when the loop is re-connected to the unit, then the loop could be shorted to 

electrical mains (and building) earth. This can happen even if no audio signal is present, as the 

short to earth is likely to cause an instability / oscillation / feedback condition to develop. A loop 

cable short to earth most commonly occurs where flat copper tape is installed on a metal-clad 

raised access flooring system. If the insulation on the flat copper tape is abraded (for example by a 

piece of metal swarf trapped below the copper tape), the conductor could short to the earthed tiles.
When installing on raised access floors, it is advisable to insulate beneath the flat copper tape 

installation using Ampetronic PWT or similar tape.
The loop short to earth may only be completed when a person steps on the tape in the affected 

location, which can create significant difficulties when diagnosing the cause of fuse failure. Contact 

Ampetronic for further advice if a unit is suffering recurring but untraceable failure of the rear panel 

fuse.

ACCESSORIES

Details of all products and services provided by Ampetronic can be found at www.ampetronic.com

Содержание MLD5

Страница 1: ...MLD5 Installation Handbook www ampetronic com...

Страница 2: ......

Страница 3: ...r other apparatus that produces heat 6 WARNING THIS APPARATUS MUST BE EARTHED GROUNDED 7 Only power cords with the correct power connector may be used to maintain safety Cables incorporating the UK 13...

Страница 4: ...d inputs These can be configured for microphone or line inputs with individually selectable phantom and gain boost For more complex installations you may need ancillary equipment such as microphone pr...

Страница 5: ...LOSS CORREC TION MLC MLC LEVEL PHASE SHIFTER AGC DISPLAY RED L E D YELLOW L E D YELLOW L E D YELLOW L E D GREEN L E D GREEN L E D PHASE SWITCH 0 90 CHANNEL CURRENT LEVEL CHANNEL CURRENT LEVEL POWER AM...

Страница 6: ...y installed according to the Designing Induction Loops handbook or as per specific design instructions provided by Ampetronic As a result a target current should be known based on achieving acceptable...

Страница 7: ...il the target current is achieved as indicated by the CH B CURRENT LEDs Headphones can be used with the MONITOR socket to listen directly to the loop current NOTE channel A output appears in the left...

Страница 8: ...o hot Loop current is not delivered to either channel See toubleshooting for details MONITOR 3 5mm jack socket for use with stereo headphones to listen to the signal being delivered to the loop POWER...

Страница 9: ...DC OUTPUT 2 pin connection for ancillary units PHASE SHIFT SELECTOR Selectable 90 phase shift between outputs XLR INPUTS Socket for balanced MIC or LINE signals INPUT GAIN BOOST SELECTOR SWITCH Gain...

Страница 10: ...ble causes for this Check the COMPRESSION LEDs are illuminating Check that the CURRENT controls are turned up sufficiently Check the LOOP or TEMP LEDs are not illuminated Ensure the Ear symbol is illu...

Страница 11: ...istance loops can be encountered in a venue with a pre installed loop which was designed for use with an old loop driver which might be being replaced Before using this loop ensure that the existing l...

Страница 12: ...1 of Instability Failed AC power fuse in rear of unit Unplug the loop and AC power supply from amplifier and replace the failed fuse with the spare fuse in AC power input fuse tray Reconnect the AC po...

Страница 13: ...le circuit Attack decay 14 5 10 7 5 10 0 2 22 100 to 5000 4 7 1 24 17 9 6 4 13 0 2 22 100 to 5000 4 7 1 45 32 13 9 2 19 0 2 24 100 to 5000 4 7 1 V A A Hz ms s STATUS SOCKET 2 pin 5mm pitch 90 header T...

Страница 14: ...35 20 90 IP20 0 35 20 90 C WARRANTY This product carries a five year parts and labour warranty from date of shipment from Ampetronic To qualify for the five year warranty the product must be register...

Страница 15: ...INSTALLATION NOTES Ampetronic MLD5 Installation Handbook Page 13...

Страница 16: ...Contents Copyright Ampetronic Ltd 2013 All rights reserved UP17601 4...

Отзывы: