FI6000 | FIRE ALARM INTERFACE
PAGE 9
Example Of Configuration
It is important to plan, sketch the task and sequence of activities required prior to configurating FI6000.
Consider a MR1301 and TD6240 are interfaced with FI6000 via RS485 ports.
If an installation with 10 zones, it is required to have : Ch 1 to trigger zone 1,2,5,6 ~ 10
.......subsequently after 5 mins, Activate Zone 1, 2, 5, 6 ~ 10, 11 ~ 15
.......subsequently after 5 mins, Activated Zone ALL Zones
When any zone is triggered at first time, activate Message 1 of MR1300 / 1 message recorder,
.......subsequently after 5 mins, message 2
.......subsequently after 5 mins, message 3
At ALL CALL, all zones shall be activated with volume controller overriding activated.
Thereby the settings for “Channel Configuration” and “ Task Configuration” shall be as shown:
Channel
Configuration
Task
Configuration
1,2,5,6-10
1,2,5,6-10,11-15
Zone
Group
1
Zone
Group
2
Use FI6000 RELAY 1 to
override volume controller