SAFETY AND OTHER WARNINGS
For safety reasons, the GG2 Detector must be installed, operated and serviced only by competent
personnel. Please read and understand this instruction manual completely before installing, operating or
servicing this equipment. Failure to install or operate this instrument in accordance with the instructions
contained in this manual may create hazardous operating conditions.
1.1 Safe Use of Equipment
The equipment supplied has been designed and manufactured to ensure safe operation. The equipment
must only be used within the design parameters.
The instructions within this manual must be observed as an aid towards achieving the safest possible
installation.
Persons responsible for installation, maintenance, or operation, must observe the following
instructions:
1.1.1 Changes to Equipment
Changes in the design and modifications to the equipment are not permitted. Unauthorised changes
made to the hardware or operating firmware will void the manufacturer's warranty, and may
compromise the integrity of the system into which it is installed and other connected equipment.
1.1.2 Equipment Knowledge
Experience with, or understanding of, this equipment is essential for the safe installation and removal of
the equipment. Therefore, please read and understand this manual prior to use. Competency based
training courses are recommended and are available on request.
1.1.3 Manual Handling
Precautions have been taken to ensure all equipment is safe to handle and free from sharp edges.
However, care should always be taken when handling enclosures and gloves should be worn.
1.1.4 Installation
Correct operation and safety depend on GG2 Detector and associated equipment being installed
correctly. Mechanical and or electrical installation and maintenance of plant and equipment must only
be carried out by appropriately qualified personnel and must be tested thoroughly prior to operation.
1.1.5 Operation
As safety depends on GG2 Detector functioning correctly it is highly recommended that all safety
functions of the unit be periodically tested to ensure correct operation. The plant used to determine or
monitor the presence of gas must be maintained in accordance with Australian Standards AS/NZS
2290.3-2018 Electrical equipment for coal mines - Maintenance and overhaul - Maintenance of gas
detecting and monitoring equipment, as amended from time to time.
1.1.5.1 Electrochemical O2 Operation
AS/NZS 4641 Electrical apparatus for detection of oxygen and other gases and vapours at toxic
levels
—General requirements and test methods, state that the concentration indicated by the output
signal shall not vary from the test gas concentration by more than a volume fraction of ±0.3% v/v over
the range 10% - 25% v/v oxygen. When exposed to other gases. Therefore, the 0-25% range Oxygen
Sensor - Electrochemical (177872) may read high when exposed to concentrations of carbon dioxide
exceeding 5%.