16
MAN3037-2
XP95 PRODUCT GUIDE
9
XP95 Manual Call Point
9.1
Operating Principles:
The XP95 EN54- 11:2001 compliant Manual Call Point (MCP) is
based on the KAC conventional MCP range. The address of each
call point is set at the commissioning stage by means of a seven-
segment DIL switch.
A single bi-coloured alarm LED is provided on the call point. This
LED is controlled, independently of the call point, by the control
panel. The red LED is lit when the call point has been activated. An
amber/yellow LED indicates a fault.
Call points can be remotely tested from the panel by transmission of a single bit in the communications
protocol. Call points respond by providing a value of 64 which corresponds to the alarm value. The panel
should recognise this response as a test signal and should not raise a general alarm.
XP95 Manual Call Points incorporate an integral short circuit isolator and are provided with a resettable
element. A backbox, for surface mounting is also provided as standard. If a glass or flush mounting tray is
required, these are available on request. Versions with a pattress box are also available.
To provide additional protection against accidental operation, a transparent hinged cover with a locking tag,
is available, which can be fitted to the manual call point.
Please note that the call point does not conform to
EN54-11:2001 when this lid is fitted and secured with the locking tag.
Figure 16 – Typical Response Characteristics – XP95 Manual Call Point
9.2
Product Codes
Product Description
Part Number
Item Number
XP95 Manual Call Point with Isolator -
Red (Surface)
55100-908AMP
213-0051
XP95 Manual Call Point - Red
(Surface)
55100-905AMP
213-0050