Page
32
LOOPSENSE EN54
INSTALLATION & COMMISSIONING
10.6.8
SmartTerminal
Termination Board Interconnection
TERMINATION BOARD No.1 ( BRD82LTB2 )
SmartTerminal 1
SmartTerminal 2
(IF FITTED)
SHIELDED COMMS CABLE
TO NEXT LCDA
MAXIMUM OF 30
LK1 MUST BE FITTED TO
THE LAST BOARD ON
THE COMMS BUS
+24VDC
TERMINATION BOARD No.2 ( BRD82LTB2 )
T O
LCD
T O
LCD
CN1
0 V
POWER OUT
POWER IN
+24V
RS485
I N
RS485
O U T
0
3
/0
5
/2
0
0
6
B
R
D
8
2
L
T
B
2
-
TB2
TB1
TB4
TB3
LK1 NOT FITTED
C O M
-
+
C O M
-
+
0 V
+24V
CN1
0V
POWER OUT
POWER IN
+24V
RS485 IN
RS485 OUT
0
3
/0
5
/2
0
0
6
B
R
D
8
2
L
T
B
2
-
TB2
TB1
TB4
TB3
COM
-
+
COM
-
+
0V
+24V
+24V
0 V
V D C
I N
V D C
O U T
0 V
USB
0V
AUX OUT1
3
2
1
OUT2
OUT1
+VE
COMMS
SGD
+VE
+VE
A+
0V
+27V
INPUTS
MONITORED O/PS
LOOP 1
LOOP 2
B-
RS485+
RS485-
SHD
2+
3+
4+
COM
1+
2+
AUX OUT2
2-
3-
4-
3+
1+
4+
1-
ETH
+27V
0V
DIAGNOSTICS RS232
RS485
TERM
LOAD
RESET
HLI
PORT
PW R IN
N/O
C
N/C
N/O
C
N/C
N/O
C
N/C
RELAY 1
RELAY 2
RELAY 3
COMMS
A-
B+
B+
A-
B-
A+
JTAG
JTAG
SEL
1
2
3
DIAGNOSTICS
CN11
TB1
U2
U1
U4
U3
TB6
R47
R1
CN1
D4
D1
D2
CN10
CN2
CN8
TB4
TB2
TB5
TB3
SW1
D3
K3
R38
R4
R5
R6
R7
10K
10K
10K
10K
10K
10K
10K
10K
CONTROLS
SHIELD
MAIN CONTROL BOARD
10.6.9 Setting the
SmartTerminal
Address
Open the front door;
locate the “CONFIG” button situated on the left hand side of the PCB
and press for 3 seconds. The buzzer and “Config” LED will double beep and flash
respectively to indicate that the Configuration mode has been entered. The LCD will now
display the Configuration screen. This screen consists of the code version number, current
address and four adjustment markers. These markers A-, A+, C-, and C+ are used to
indicate the keys that adjust the address and LCD contrast.
Use the “PREVIOUS (A-) and NEXT” (A+) keys to select the desired address. The default
value for this address is 255 which is not a valid SmartTerminal address. The user must then
select an address value from 1 to 30, i.e. the same address as that set in the FACP. The
keys corresponding to C- (SILENCE BUZZER) and C+ (RESET) are used in a similar
manner to decrease and increase the LCD contrast level. There is audible feedback for all
key presses.
Once the address has been set press the “CONFIG” button again for 3 seconds and the
screen will return t
o its default and the “DIAGNOSTIC” LED will return to a slow flash. This
slow flash indicates SmartTerminal and the FACP are communicating normally i.e. the LED
flashes if communications data is being received from the FACP.
Note:
If the address is not set within the time out period of approximately 75 seconds
SmartTerminal
will return to its previous state.