Outdoor LoRa Data Logger
20
Connect to devices via DIs / DO (Digital Input / Digital Output) :
The OOT550 provides 2 DI ports and 1 DO port for connecting to those digital sensor/meter devices. To
connect the device, you have to identify the type of your device and properly connect and configure the
OOT550 so that it can get the correct readings from the connected devices.
The DI port supports either Pulse counter mode, or just a Dry contact. Since the OOT550 can not detect what
kind of device is connected to, not only hardware configuration (
CON4
) is required, but also software
configuration is mandatory.
Pinout Definition @ CON4
Pin9
Pin10
Pin11
Pin12
Pin13
Pin14
Pin15
Pin16
DO+
DO-
DI1+
DI1-
GND
DI2+
DI2-
GND
Digital I/O Specification
I / O
Specification
Digital Input
(Isolated)
Trigger Voltage (high)
Logic level 1: 2V~25V
Normal Voltage (low)
Logic level 0: 0V~1V, or floating
Digital Output
(Isolated)
Non-Relay mode
Maximum 24V/300mA
(Depends on external device)
Example of Connection Diagram - DI