![amiad ICS-TCP Series Скачать руководство пользователя страница 28](http://html.mh-extra.com/html/amiad/ics-tcp-series/ics-tcp-series_installation-operation-and-maintenance-instructions_2932283028.webp)
Page 7
Rev: 091014
Operating and Maintenance
Manual
P
a
g
e
7
Transformer
The transformer steps the high voltage down to a usable low voltage for the control components. It is
protected with fuses on the primary side and circuit breakers on the secondary side. Exchanging the
short-circuit protection of the controller should be exact one for one. Never increase the short circuit
protection of the controller without consulting the Factory Controls Engineer first. It is CE-marked, UL
approved, and conforms to most international standards.
Adjustable Flush Interval Timer
This timer allows the end-user to define the minimum flush interval time. This is very important to
ensure efficiency of the filter. Standard factory setting is to allot for a flush cycle every day. This timer is
a high performance timer with 8A contacts and the ability to set the interval from 0.05s-60hr. It is CE-
marked, UL approved, and conforms to most international standards.
Adjustable Flush Duration
The flush cycle can be adjusted through this timer. The ability to set the time as low as 0.15s-3min
makes this timer very versatile over a number of different applications. The timer starts from a variety
of start inputs. Different filter types require different time durations. Contact your local sales
representative for this parameter. It is CE-marked, UL approved, and conforms to most international
standards.
Note for first-time startup:
If the Start Input is not cleared within the flush duration, it will come out of flush, and will not go back
into flush cycle until a hard reset. This can be done by cycling power.
3-Way Flush-Auto-Off
This front switch allows the user to locally enable a flush cycle, disable/reset the flush cycle or to allow it
to run the filter in Auto mode. The flush position is spring return to ensure that the flush cycle is not
constant. It is CE-marked, UL approved, and conforms to most international standards.
Power On Light
This LED light is for local indication that the power is on, and ready for flushing. It is CE-marked, UL
approved, and conforms to most international standards.
3.3 Transportation
The system can only be transported with the disconnect switch turned to the off position, and the
power isolated.
28 of 34
Содержание ICS-TCP Series
Страница 11: ...11 of 34 ...
Страница 12: ...12 of 34 ...
Страница 13: ...13 of 34 ...
Страница 14: ...14 of 34 ...
Страница 15: ...15 of 34 ...
Страница 16: ...16 of 34 ...
Страница 17: ...17 of 34 ...
Страница 18: ...18 of 34 ...
Страница 19: ...19 of 34 ...
Страница 22: ...Amiad USA INC Level I Filter Controller UL 508A Standard 22 of 34 ...
Страница 32: ...Page 11 Rev 091014 Operating and Maintenance Manual Page 11 32 of 34 ...