Data and Alarm Channel Configuration 

The 

AMG5526 

sends and receives data from an 

AMG5515

 or rackmount equivalent 

AMG5515R 

dual 

channel

 

transmit unit. Each physical data interface RS-485, RS-422 or RS-232 is individually 

selectable by the user with the corresponding slide switch mounted on the main PCB inside the 
enclosure.  
 
2 uni-directional alarms are also provided for each channel, each of which can receive an on/off signal 
from an 

AMG5515

 and are typically used to convey contact closure status. Each alarm output uses a 

Solid-state relay, with a maximum load current of 150mA at 125Vac/dc and Ron < 6.5Ω. 
 

 

 

 

 

Data Channel Configuration 

Each low speed data channel provides an RS-232, RS-422 (full duplex, four wire) or RS-485 (half 
duplex, two wire) interface defined by the corresponding mode switch inside the enclosure. Every data 
channel as shipped from the factory is set up for RS-485 operation unless otherwise requested. 
 
The data input for both the RS-485 and the RS-422 modes detects a tri-state input condition by 
monitoring the differential voltage level across the input. A differential level below 600mV positive or 
negative will be detected as a tri-state condition. A level above 600mV positive or negative will be 
detected as a logic 1 or logic 0 respectively. It is important therefore to terminate the RS-485 bus or 
the RS-422 input bus using 120Ω if a pre-bias is present on the RS-485 or RS-422 bus.  
 
A large number of third party equipment manufacturers apply a pre-bias on their RS-485 bus. This pre-
bias is applied by pulling one arm of the RS-485 bus high (+5 volts) and the other arm low (0 volts) 
using high value resistors within the third party equipment. In order to ensure that the AMG equipment 
detects a tri-state condition, then these resistors should have a value above 5kΩ.  If the third party 
bias resistors are less the 750Ω the bus can be multiple terminated as required to ensure that a tri-
state level is detected. 
 

Содержание AMG5526

Страница 1: ...l and two Uni directional Alarms for a Singlemode Fibre Link The AMG5526 is a DUAL standalone system which provides two independent channels each designed to receive 2 uni directional alarms and trans...

Страница 2: ...Optical Connection 3 Connections 4 Optical Connections Singlemode 4 Power Connection 4 Data and Alarm Channel Connections 4 Front Panel Indicators 5 Power Opto LED 5 Low Speed Data LEDs 5 Alarm LEDs 5...

Страница 3: ...ceive channels Each channel receives 1 data and 2 uni directional alarm signals from up to two AMG5515 single channel or one dual channel transmit unit It also transmits 1 data signal to each AMG5515...

Страница 4: ...Optical Dynamic Range 20dB Power Connection Connector Type Removable 2 pin 3 81mm Screw Terminal Connector Partno Phoenix 1803578 Supply Voltage 12 to 15 Volts DC Maximum Power 2 5 Watts Data and Alar...

Страница 5: ...ansitions present on input IN Off logic one V present on input IN IN corresponds to the data signals being transmitted onto the optical fibre Data Present OUT RS485 or RS422 Green logic zero V V prese...

Страница 6: ...ce defined by the corresponding mode switch inside the enclosure Every data channel as shipped from the factory is set up for RS 485 operation unless otherwise requested The data input for both the RS...

Страница 7: ...iddle RS 232 switch bottom 1 IN A IN 2 IN B 3 GND GND GND 4 5 6 7 IN OUT A OUT A 8 IN OUT B OUT B OUT Note A or B in brackets in the above table refers to RS 485 RS 422 data specification Alarm Channe...

Страница 8: ...g screws on the rear panel and slide the PCB sufficiently out of the case to enable access to the switch To replace the PCB into the case slide the PCB gently into the case if necessary aligning the b...

Отзывы: