In rooms with ceiling falls to 20cm, the smoke detector can be mounted on the
fall. In rooms with ceiling falls over 20cm on both sides should be a smoke
detector.
Smoke detectors in hallways and corridors: With a max. width of 3m the allowed
distance between two smoke detectors is max. 15 m. The distance from one end
of the corridor or passage to the other must not exceed 7.5m.
Smoke detectors in draughty points: to avoid that the smoke does not reach the
smoke detectors, they must not be installed near climate and ventilation
openings.
Assembly of the magnetic pads
The above example shows you the way of mounting our smoke detector without drilling.
For this, you take the smoke detector and connect it with the magnetic pad to the ceiling.
The Magnet Pad should be glued offset to the ceiling mount so that it is located under the
test button. This has the advantage, that the smoke detector is stable on the magnetic
holder when pressing the test button.