Basic Operation
Sorensen DCS-E Series 3kW Supplies
3-2
M362295-01 Rev D
•
the resistance of the attached load R
L
.
Figure 3-1 provides a graphical representation of the relationships between these variables.
C
ONSTANT
V
OLTAGE
M
ODE
O
PERATION
The power supply will operate in constant voltage mode whenever the load current I
L
is less
than the current limit setting I
SET
, or: I
L
< I
SET
(Note: I
L
= V
SET
/ R
L
)
In constant voltage mode, the power supply maintains the output voltage at the selected value
(V
SET
) while the load current I
L
varies with the load requirements.
C
ONSTANT
C
URRENT
M
ODE
O
PERATION
The power supply will operate in constant current mode whenever the load resistance is low
enough that the load current I
L
is greater than the current limit setting I
SET
, or: I
L
> I
SET
In constant current mode, the power supply maintains the output current at the selected value
(I
SET
) while the load voltage varies with the load requirements.
Figure 3-1 Operating Modes
A
UTOMATIC
M
ODE
C
ROSSOVER
This feature allows the power supply to automatically switch operating modes in response to
changing load requirements. If, for instance, the power supply was operating in Constant
Voltage Mode (I
L
< I
SET
), and the load changed so that the load current (I
L
) became greater
than the current limit setting (I
SET
), the power supply would automatically switch into Constant
Current Mode. If the additional load was subsequently removed so that the load current was
again less than the current limit setting, the supply would automatically return to Constant
Voltage Mode.
Содержание Sorensen DC Series
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 6: ...ii This page intentionally left blank...
Страница 8: ...iv This page intentionally left blank...
Страница 10: ...vi This page intentionally left blank...
Страница 12: ...viii This page intentionally left blank...
Страница 24: ...Introduction Sorensen DCS E Series 3kW Supplies 1 6 M362295 01 Rev D This page intentionally left blank...
Страница 38: ...Installation Sorensen DCS E Series 3kW Supplies 2 14 M362295 01 Rev D This page intentionally left blank...
Страница 44: ...Basic Operation Sorensen DCS E Series 3kW Supplies 3 6 M362295 01 Rev D This page intentionally left blank...
Страница 70: ...Advanced Operation Sorensen DCS E Series 3kW Supplies 4 26 M362295 01 Rev D This page intentionally left blank...
Страница 86: ...Theory of Operation Sorensen DCS E Series 3kW Supplies 5 16 M362295 01 Rev D This page intentionally left blank...
Страница 92: ...Maintenance Sorensen DCS E Series 3kW Supplies 6 6 M362295 01 Rev D This page intentionally left blank...