![Ametek Powervar ABCE422 Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/ametek/powervar-abce422/powervar-abce422_manual_2931408030.webp)
30
A01-00055 Rev N
North American Models ABCE802-11 and ABCE802-11MED
ABCE802-11
50080-03R
ABCE802-11MED
50080-23R
Type
Standard
Medical Grade
Power Rating (VA/Watts)
800 / 720
800 / 720
Inverter Waveform
Low Distortion Sine Wave
Low Distortion Sine Wave
Transfer Time
4 ms. Typical
4 ms. Typical
Frequency
60 Hz.
60 Hz.
BTU/Hr.
231
231
T.H.D. w/100% Resistive Load
<4% on Battery
<4% on Battery
Online Efficiency (w/o Charger)
91%
91%
Input Voltage
120
120
Input Current
9.35 Amps
9.35 Amps
Output Voltage
120
120
Output Current (VA/Watts)
6.70 / 6.00 Amps
6.70 / 6.00 Amps
Input Voltage Range
(w/o Using Battery)
96 to 144 Volts
96 to 144 Volts
Output Regulation (On Mains)
± 10%
± 10%
Output Regulation (On Battery)
± 5%
± 5%
Backup Time at Full Load (0.7 P.F.)
5 Minutes
5 Minutes
Floor Mountable
Yes (Optional)
Yes (Optional)
Communications Interface
DB9, USB (SNMP Optional)
DB9, USB (SNMP Optional)
Shipping Weight (lbs.)
49
49