26
A01-00055 Rev N
6.0 SPECIFICATIONS
North American Models ABCE422-11 and ABCE422-11MED
ABCE422-11
50042-02R
ABCE422-11MED
50042-22R
Type
Standard
Medical Grade
Power Rating (VA/Watts)
420 / 378
420 / 378
Inverter Waveform
Low Distortion Sine Wave
Low Distortion Sine Wave
Transfer Time
4 ms. Typical
4 ms. Typical
Frequency
60 Hz.
60 Hz.
BTU/Hr.
140
140
T.H.D. w/100% Resistive Load
<4% On Battery
<4% On Battery
Online Efficiency (w/o Charger)
90%
90%
Input Voltage
120
120
Input Current
5.18 Amps
5.18 Amps
Output Voltage
120
120
Output Current (VA/Watts)
3.50 / 3.20 Amps
3.50 / 3.20 Amps
Input Voltage Range
(w/o Using Battery)
96 to 144 Volts
96 to 144 Volts
Output Regulation (On Mains)
± 10%
± 10%
Output Regulation (On Battery)
± 5%
± 5%
Backup Time at Full Load (0.7 P.F.)
5 Minutes
5 Minutes
Floor Mountable
Yes (Optional)
Yes (Optional)
Communications Interface
DB9, USB
DB9, USB
Shipping Weight (lbs.)
37
37