Section A
Page 3
FTI-Eb Fixed Thermal Imaging System
Installation Guide
Digital Input via NUDAM 6052 Isolated Digital Input Modules
6 bits isolated digital input
VIL:
1V
max
VIH:
3.5V
min
(24V
max)
Impedance
1.2KΩ
Isolation
5000V
rms
Relay Output via NUDAM 6063 Relay Output Module
7 isolated relay outputs
Output type:
form A
Contact rating:
AC 0.5A,125V
DC
1A,
30V
Isolation:
1000 MΩ @ 500V DC
Analog Input via NUDAM 6018 Thermocouple Analog Input Module
6 differential analog inputs
Max common mode (wrt AGND): 30V
Isolation:
2500V
rms
Input:
programmable mV, V, mA, thermocouple
Analog Output via NUDAM 6024 4 Channel Analog Output Module
4 bipolar analog outputs
Isolation:
2500V
rms
Output:
programmable